6AG1336-4GE00-4AB0
SIPLUS S7-300 SM336 6AE F

From SIEMENS

***SPARE PART*** SIPLUS S7-300 SM 336F 6AI HART for medial exposure with conformal coating based on 6ES7336-4GE00-0AB0
Supply voltage
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
From power supply L+, typ.150 mA
from backplane bus 5 V DC, max.90 mA
Power loss
Power loss, typ.4.5 W
Analog inputs
Number of analog inputs6
permissible input current for current input (destruction limit), max.40 mA
Input ranges
VoltageNo
CurrentYes
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)150 Ω; typ. 150 ohms max. 175 ohms
4 mA to 20 mAYes
Input resistance (4 mA to 20 mA)150 Ω; typ. 150 ohms max. 175 ohms
Cable length
shielded, max.1 000 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 15 bit + sign
Integration time (ms)20 ms @ 50 Hz, 16.7 ms @ 60 Hz
Interference voltage suppression for interference frequency f1 in Hzf=n x (f1 ±0.5 %)
Encoder
Connection of signal encoders
for current measurement as 2-wire transducerYes
for current measurement as 4-wire transducerYes
Errors/accuracies
Operational error limit in overall temperature range
Current, relative to input range, (+/-)0.2 %; 40 µA
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)0.1 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Diagnostics indication LED
Fail-safe operationYes
Group error SF (red)Yes
Encoder supply Vs (green)No
Potential separation
Potential separation analog inputs
between the channelsYes
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with370V for 1 min
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
FM approvalYes
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Highest safety class achievable in safety mode
acc. to EN 9544
SIL acc. to IEC 61508SIL 3
Ambient conditions
Ambient temperature during operation
min.0 °C; = Tmin
max.60 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.350 g
last modified:03/13/2019