6AG1332-8TF01-4AB0
SIPLUS S7-300 SM332 8AO HART

From SIEMENS

***Spare part*** SIPLUS S7-300 SM 332 8AO HART for medial exposure with conformal coating based on 6ES7332-8TF01-0AB0
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.350 mA
from backplane bus 5 V DC, max.110 mA
Power loss
Power loss, typ.6 W
Analog outputs
Number of analog outputs8
Current output, no-load voltage, max.24 V
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mANo
4 mA to 20 mAYes
Load impedance (in rated range of output)
with current outputs, max.750 Ω
with current outputs, inductive load, max.10 mH
Cable length
shielded, max.800 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Settling time
for resistive load0.1 ms
for inductive load0.5 ms
Errors/accuracies
Operational error limit in overall temperature range
Current, relative to output range, (+/-)0.2 %
Basic error limit (operational limit at 25 °C)
Current, relative to output range, (+/-)0.1 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog outputs
between the channels and backplane busYes
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
FM approvalYes
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50121-4No
EN 50155No
Ambient conditions
Ambient temperature during operation
min.0 °C; = Tmin
max.60 °C; = Tmax
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.220 g