| SIPLUS S7-300 SM 332 8AO HART -25...+60°C with conformal coating based on 6ES7332-8TF01-0AB0 . Analog output 8 AO 0/4-20 mA HART, for ET 200M with IM 153-2, IM 153-2, 20-pole Functions: FW update, HART auxiliary variables, redundancy, local diagnostic buffer with time stamping, Requirement: PCS 7 V7.0, SP1 |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 350 mA |
from backplane bus 5 V DC, max. | 110 mA |
Power loss |
Power loss, typ. | 6 W |
Analog outputs |
Number of analog outputs | 8 |
Current output, no-load voltage, max. | 24 V |
Output ranges, current |
0 to 20 mA | Yes |
-20 mA to +20 mA | No |
4 mA to 20 mA | Yes |
Load impedance (in rated range of output) |
with current outputs, max. | 750 Ω |
with current outputs, inductive load, max. | 10 mH |
Cable length |
shielded, max. | 800 m |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit |
Settling time |
for resistive load | 0.1 ms |
for inductive load | 0.5 ms |
Errors/accuracies |
Operational error limit in overall temperature range |
Current, relative to output range, (+/-) | 0.2 %; ±0.4 % @ < 0 °C or > 60 °C |
Basic error limit (operational limit at 25 °C) |
Current, relative to output range, (+/-) | 0.1 % |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Substitute values connectable | Yes |
Alarms |
Diagnostic alarm | Yes |
Diagnostic messages |
Diagnostic information readable | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Potential separation |
Potential separation analog outputs |
between the channels and backplane bus | Yes |
Isolation |
Isolation tested with | 500 V DC |
Standards, approvals, certificates |
CE mark | Yes |
UL approval | Yes; File E239877 |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | Yes |
Ambient conditions |
Ambient temperature during operation |
min. | -25 °C; = Tmin |
max. | 60 °C; = Tmax |
Ambient temperature during storage/transportation |
min. | -40 °C |
max. | 70 °C |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 5 000 m |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
Use on ships/at sea |
— to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
— to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
Remark |
— Note regarding classification of environmental conditions acc. to EN 60721 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
Connection method |
required front connector | 20-pin |
Dimensions |
Width | 40 mm |
Height | 125 mm |
Depth | 117 mm |
Weights |
Weight, approx. | 220 g |
last modified: | 03/13/2019 |