6AG1332-8TF01-2AB0
SIPLUS SM332 8AO HART

From SIEMENS

SIPLUS S7-300 SM 332 8AO HART -25...+60°C with conformal coating based on 6ES7332-8TF01-0AB0 . Analog output 8 AO 0/4-20 mA HART, for ET 200M with IM 153-2, IM 153-2, 20-pole Functions: FW update, HART auxiliary variables, redundancy, local diagnostic buffer with time stamping, Requirement: PCS 7 V7.0, SP1
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.350 mA
from backplane bus 5 V DC, max.110 mA
Power loss
Power loss, typ.6 W
Analog outputs
Number of analog outputs8
Current output, no-load voltage, max.24 V
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mANo
4 mA to 20 mAYes
Load impedance (in rated range of output)
with current outputs, max.750 Ω
with current outputs, inductive load, max.10 mH
Cable length
shielded, max.800 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Settling time
for resistive load0.1 ms
for inductive load0.5 ms
Errors/accuracies
Operational error limit in overall temperature range
Current, relative to output range, (+/-)0.2 %; ±0.4 % @ < 0 °C or > 60 °C
Basic error limit (operational limit at 25 °C)
Current, relative to output range, (+/-)0.1 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog outputs
between the channels and backplane busYes
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.60 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.220 g
last modified:03/13/2019

External links