6AG1331-7PF01-4AB0
SIPLUS SM331 8AI

From SIEMENS

SIPLUS S7-300 SM 331 8AI with conformal coating based on 6ES7331-7PF01-0AB0 . Analog input isolated, 2/3/4-wire, 8 AI, Resistor, Pt100/200/1000 NI100/120/200/500/1000, CU10, characteristics according to GOST 16 (internal 24) bit, 50ms, 1x 40-pole
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.240 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.4.6 W
Analog inputs
Number of analog inputs8
For resistance measurement8
permissible input voltage for voltage input (destruction limit), max.75 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20)
Input ranges
VoltageNo
CurrentNo
ThermocoupleNo
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), voltages
0 to +10 VNo
1 V to 5 VNo
1 V to 10 VNo
-1 V to +1 VNo
-10 V to +10 VNo
-2.5 V to +2.5 VNo
-250 mV to +250 mVNo
-5 V to +5 VNo
-50 mV to +50 mVNo
-500 mV to +500 mVNo
-80 mV to +80 mVNo
Input ranges (rated values), currents
0 to 20 mANo
-10 mA to +10 mANo
-20 mA to +20 mANo
-3.2 mA to +3.2 mANo
4 mA to 20 mANo
Input ranges (rated values), thermocouples
Type BNo
Type CNo
Type ENo
Type JNo
Type KNo
Type LNo
Type NNo
Type RNo
Type SNo
Type TNo
Type UNo
Type TXK/TXK(L) to GOSTNo
Input ranges (rated values), resistance thermometer
Cu 10Yes
Ni 100Yes
Ni 1000Yes
LG-Ni 1000Yes
Ni 120Yes
Ni 200Yes
Ni 500Yes
Pt 100Yes
Pt 1000Yes
Pt 200Yes
Pt 500Yes
Input ranges (rated values), resistors
0 to 150 ohmsYes
0 to 300 ohmsYes
0 to 600 ohmsYes
Characteristic linearization
parameterizableYes
— for resistance thermometerPt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10; (standard/climate)
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; Two's complement
Integration time, parameterizableYes
Basic conversion time (ms)up to 4 channels: 10 ms per module, over 5 channels: 190 ms per module, 8 channels: 80 ms
Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 Hz
Encoder
Connection of signal encoders
for resistance measurement with two-wire connectionYes; without resistance correction
for resistance measurement with three-wire connectionYes
for resistance measurement with four-wire connectionYes
Errors/accuracies
Operational error limit in overall temperature range
Resistance, relative to input range, (+/-)0.1 %
Resistance thermometer, relative to input range, (+/-)±1 K
Basic error limit (operational limit at 25 °C)
Resistance, relative to input range, (+/-)0.05 %
Resistance thermometer, relative to input range, (+/-)±0.5 K
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable per group
Limit value alarmYes; Parameterizable
Hardware interruptYes; Parameterizable, channels 0 to 7
Diagnostic messages
Diagnostic information readableYes
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog inputs
between the channels and backplane busYes
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50121-4No
EN 50155No
Ambient conditions
Ambient temperature during operation
min.0 °C; = Tmin
max.60 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector40-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.272 g
last modified:03/25/2019

External links