6AG1331-7NF10-2AB0
SIPLUS SM331 8AI - 40pol

From SIEMENS

SIPLUS S7-300 SM 331 8AI 40-pole -25...+60°C with conformal coating based on 6ES7331-7NF10-0AB0 . Analog "input isolated, ""8 AI; +/-5/10" V, 1-5 V, +/-20 mA, 0/4 to 20 mA, 16 bit, Single rooting (60 V COM.), 4-channel operation: 10 ms, 8-channel operation: 23-95ms, 1x 40-pole
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.200 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.3 W
Analog inputs
Number of analog inputs8
permissible input voltage for voltage input (destruction limit), max.75 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20)
permissible input current for current input (destruction limit), max.40 mA
Input ranges
VoltageYes
CurrentYes
ThermocoupleNo
Resistance thermometerNo
ResistanceNo
Input ranges (rated values), voltages
0 to +10 VNo
1 V to 5 VYes
Input resistance (1 V to 5 V)10 MΩ
1 V to 10 VNo
-1 V to +1 VNo
-10 V to +10 VYes
Input resistance (-10 V to +10 V)10 MΩ
-2.5 V to +2.5 VNo
-250 mV to +250 mVNo
-5 V to +5 VYes
Input resistance (-5 V to +5 V)10 MΩ
-50 mV to +50 mVNo
-500 mV to +500 mVNo
-80 mV to +80 mVNo
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)250 Ω
-20 mA to +20 mAYes
Input resistance (-20 mA to +20 mA)250 Ω
-3.2 mA to +3.2 mANo
4 mA to 20 mAYes
Input resistance (4 mA to 20 mA)250 Ω
Input ranges (rated values), thermocouples
Type BNo
Type CNo
Type ENo
Type JNo
Type KNo
Type LNo
Type NNo
Type RNo
Type SNo
Type TNo
Type UNo
Type TXK/TXK(L) to GOSTNo
Input ranges (rated values), resistance thermometer
Cu 10No
Ni 100No
Ni 1000No
LG-Ni 1000No
Ni 120No
Ni 200No
Ni 500No
Pt 100No
Pt 1000No
Pt 200No
Pt 500No
Input ranges (rated values), resistors
0 to 150 ohmsNo
0 to 300 ohmsNo
0 to 600 ohmsNo
0 to 6000 ohmsNo
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; Unipolar: 15/15/15/15 bit; bipolar: 15 bit + sign/15 bit + sign/15 bit + sign/15 bit + sign
Integration time, parameterizableYes; 23 / 72 / 83 / 95 ms
Basic conversion time (ms)10 ms (4-channel mode); 95/83/72/23 ms (8-channel mode)
Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 Hz, combinations of 400, 60, 50 Hz
Encoder
Connection of signal encoders
for current measurement as 2-wire transducerYes; with external transmitter, current supply; possible with separate supply for transmitter
for current measurement as 4-wire transducerYes
Errors/accuracies
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.1 %; @ 0 ... +60 °C; ±0.2% @ -25 ... +60 °C
Current, relative to input range, (+/-)0.1 %; @ 0 ... +60 °C; ±0.2% @ -25 ... +60 °C
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.05 %
Current, relative to input range, (+/-)0.05 %
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Limit value alarmYes; Parameterizable all channels (end of cycle interrupt is also supported across modules)
Hardware interruptYes; Parameterizable, channels 0 to 7 (on exceeding limit value), at end of cycle
Diagnostic messages
Diagnostic information readableYes
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog inputs
between the channels and backplane busYes
Isolation
Isolation tested with500 V AC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50121-4No
EN 50155No
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.60 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector40-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.272 g
last modified:03/13/2019

External links