6AG1326-1BK02-2AB0
SIPLUS S7-300 SM326F DI24

From SIEMENS

SIPLUS S7-300 SM 326F DI24 40-pole -25...+60°C (70°C with forced convection) with conformal coating based on 6ES7326-1BK02-0AB0 . Digital input F-DI 24x24 V DC Fail-safe digital input for SIMATIC S7 F-systems with diagnostic alarm
Supply voltage
Rated value (DC)24 V
Input current
from load voltage L+ (without load), max.450 mA
from backplane bus 5 V DC, max.100 mA
Encoder supply
Number of outputs4; Isolated
Output current
Rated value400 mA
Power loss
Power loss, typ.10 W
Digital inputs
Number of digital inputs24
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.24
— up to 60 °C, max.24; (at 24 V) or 18 (at 28.8 V)
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"-30 to +5V
for signal "1"+11 to +30V
Input current
for signal "0", max. (permissible quiescent current)2 mA
for signal "1", typ.10 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", max.3.4 ms
— at "1" to "0", max.3.4 ms
Cable length
shielded, max.200 m
unshielded, max.100 m
Encoder
Connectable encoders
2-wire sensorYes; if short-circuit test is deactivated
— permissible quiescent current (2-wire sensor), max.2 mA
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Diagnostics indication LED
Fail-safe operationYes
Group error SF (red)Yes
Ex(i) characteristics
Maximum values of input circuits (per channel)
Ta (permissible ambient temperature), max.60 °C
Potential separation
Potential separation digital inputs
between the channelsYes
between the channels, in groups of12
between the channels and backplane busYes
Isolation
Isolation tested with500 V DC/350 V AC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Highest safety class achievable in safety mode
acc. to DIN VDE 0801AK 6
acc. to EN 954Cat. 4
SIL acc. to IEC 61508SIL 3
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.60 °C; = Tmax; *+70 °C where forced convection with a minimum air velocity of 0.7 m/s through the modules and rated voltage of 24 V ±5 % are ensured. If in the course of maintenance or automatic diagnosis it is determined that the admissible specified parameters have been exceeded, the modules should be subjected to a proof test (function check) by the manufacturer.
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector40-pin
Dimensions
Width80 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.442 g