6AG1322-1CF00-7AA0
SIPLUS SM322 8DA/48-125VDC

From SIEMENS

SIPLUS S7-300 SM 322 8DO 48-125V -25...+70°C with conformal coating based on 6ES7322-1CF00-0AA0 . Digital output isolated, 8 DO, 48-125 V DC, 1.5A, 1x 20-pole
Supply voltage
Load voltage L+
Rated value (DC)48 V; 48 V DC to 125 V DC
permissible range, lower limit (DC)40 V
permissible range, upper limit (DC)140 V
Input current
from load voltage L+ (without load), max.2 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.7.2 W
Digital outputs
Number of digital outputs8
Limitation of inductive shutdown voltage toM (-1 V)
Switching capacity of the outputs
on lamp load, max.15 W; 15 W (48 V) or 40 W (125 V)
Output voltage
for signal "1", min.L+ (-1.2 V)
Output current
for signal "1" rated value1.5 A
for signal "1" minimum load current10 mA
for signal "1" permissible surge current, max.3 A; for 10 ms
for signal "0" residual current, max.0.5 mA
Switching frequency
with resistive load, max.25 Hz
with inductive load, max.0.5 Hz
on lamp load, max.10 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.6 A
— up to 60 °C, max.3 A
— up to 70 °C, max.1 A
vertical installation
— up to 40 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionNo
Alarms
Diagnostic alarmNo
Diagnostic messages
Wire-breakNo
Short-circuitNo
Fuse blownNo
missing load voltageNo
Diagnostics indication LED
Rated load voltage PWR (green)No
Fuse OK FSG (green)No
Group error SF (red)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital outputs
between the channelsYes
between the channels, in groups of4
between the channels and backplane busYes; Optocoupler
Permissible potential difference
between different circuits146 V DC/132 V AC
Isolation
Isolation tested with1500 V AC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50155Yes; T1 Category 1 Class A/B horizontal mounting position
Ambient conditions
Ambient temperature during operation
min.-25 °C
max.70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.250 g
last modified:03/13/2019