6AG1321-7BH01-2AB0
SIPLUS SM321 16DE/24VDC

From SIEMENS

SIPLUS S7-300 SM 321-20-pole -25...+70°C with conformal coating Conformity with EN 50155 T1 Kat 1 Kl A/B based on 6ES7321-7BH01-0AB0. Digital "input Isolated ""16 DI; 24 V DC," "1x 20-pole,"" process interrupt," diagnostics, suitable for isochronous mode operation
Supply voltage
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
from load voltage L+ (without load), max.90 mA
from backplane bus 5 V DC, max.130 mA
Power loss
Power loss, typ.4 W
Digital inputs
Number of digital inputs16
Input characteristic curve in accordance with IEC 61131, type 2Yes
Number of simultaneously controllable inputs
horizontal installation
— up to 60 °C, max.16
vertical installation
— up to 40 °C, max.16
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"-30 to +5V
for signal "1"13 to 30V
Input current
for signal "1", typ.7 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableYes; 0.1 / 0.5 / 3 / 15 / 20 ms
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.2 mA
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Hardware interruptYes; Parameterizable
Diagnostic messages
Wire-breakYes; to I< 1 mA
Diagnostics indication LED
Group error SF (red)Yes
Status indicator digital input (green)Yes
Potential separation
Potential separation digital inputs
between the channelsNo
between the channels, in groups of16
between the channels and backplane busYes; Optocoupler
Permissible potential difference
between different circuits75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Use in hazardous areas
ATEXYes
Railway application
EN 50155Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B, EN 50155:2007
Ambient conditions
Ambient temperature during operation
min.-25 °C
max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.200 g
last modified:03/25/2019