SIPLUS ET 200S EM 2AI RTD -25...+70°C with conformal coating based on 6ES7134-4JB51-0AB0
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.30 mA
from backplane bus 3.3 V DC, max.10 mA
Output voltage
Power supply to the transmitters
presentYes
short-circuit proofYes
Power loss
Power loss, typ.0.6 W
Address area
Address space per module
Address space per module, max.8 byte
Analog inputs
Number of analog inputs4; 2 for 3 or 4-wire connection
permissible input voltage for voltage input (destruction limit), max.9 V
Constant measurement current for resistance-type transmitter, typ.1.67 mA
Cycle time (all channels) max.Number of active channels per module x basic conversion time
Technical unit for temperature measurement adjustableNo
Input ranges (rated values), resistance thermometer
Ni 100Yes; Standard/climate
Input resistance (Ni 100)2 000 kΩ
Pt 100Yes; Standard/climate
Input resistance (Pt 100)2 000 kΩ
Input ranges (rated values), resistors
0 to 150 ohmsYes
Input resistance (0 to 150 ohms)2 000 kΩ
0 to 300 ohmsYes
Input resistance (0 to 300 ohms)2 000 kΩ
0 to 600 ohmsYes
Input resistance (0 to 600 ohms)2 000 kΩ
Characteristic linearization
parameterizableYes; for Pt100, Ni100
— for resistance thermometerPt100 (standard, climatic range), Ni100 (standard, climatic range)
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 150 ohms: 14 bit; 300, 600 ohms: 15 bit, Pt100, Ni100: 16 bit
Integration time, parameterizableYes
Integration time (ms)16,7 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Conversion time (per channel)66 / 80 ms; additional conversion time for diagnostic wire break test
Smoothing of measured values
parameterizableYes; In four stages by means of digital filtering
Step: NoneYes; 1x cycle time
Step: lowYes; 4x cycle time
Step: MediumYes; 32x cycle time
Step: HighYes; 64x cycle time
Encoder
Connection of signal encoders
for resistance measurement with two-wire connectionYes
for resistance measurement with three-wire connectionYes
for resistance measurement with four-wire connectionYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Resistance thermometer, relative to input range, (+/-)0.6 %
Basic error limit (operational limit at 25 °C)
Resistance thermometer, relative to input range, (+/-)0.4 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode interference (USS < 2.5 V) , min.90 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Diagnostic messages
Wire-breakYes
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Diagnostics wire breakDisable / enable
Measurement type/rangedeactivated/150 ohms/; 300 ohms/600 ohms/ Pt100 climatic/ Pt100 standard; Ni100 standard / Ni100 climatic, 2, 3 or 4-wire
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between MANA and M internally (UISO)75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g