6AG1132-4BD02-7AA0
SIPLUS ET200S 4DO (1VE = 5 Stueck)

From SIEMENS

SIPLUS ET 200S EM 4DO Standard -25...+70°C with conformal coating based on 6ES7132-4BD02-0AA0 . Electronic module 24 V DC/0.5A 15 mm width, 5 units per packing unit
Supply voltage
Reverse voltage protectionYes; when using the same load voltage as on the power module
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes; polarity reversal can lead to the digital outputs being connected through
Input current
from load voltage L+ (without load), max.10 mA; Per channel
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, typ.0.8 W
Address area
Address space per module
Address space per module, max.1 byte
with packing4 bit
Digital outputs
Number of digital outputs4
Short-circuit protectionYes
Response threshold, typ.1 to 1.5 A
Controlling a digital inputYes
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit3 400 Ω
Output voltage
for signal "1", min.L+ (-1 V)
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range, min.7 mA
for signal "1" permissible range, max.600 mA
for signal "0" residual current, max.0.3 mA
Output delay with resistive load
"0" to "1", max.45 µs; Typical value
"1" to "0", max.90 µs; Typical value
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes; per module
Switching frequency
with resistive load, max.800 Hz
with inductive load, max.2 Hz
on lamp load, max.10 Hz
Total current of the outputs
Current per module, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes
Interrupts/diagnostics/status information
Diagnostics functionNo
Diagnostics indication LED
Status indicator digital output (green)Yes
Parameter
Remark1 byte
Potential separation
Potential separation digital outputs
between the channelsNo
between the channels and backplane busYes
Isolation
Isolation tested with500 V DC
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g
last modified:03/25/2019