| SIPLUS ET 200S EM 4DO Standard -25...+70°C with conformal coating based on 6ES7132-4BD02-0AA0 . Electronic module 24 V DC/0.5A 15 mm width, 5 units per packing unit |
Supply voltage |
Reverse voltage protection | Yes; when using the same load voltage as on the power module |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes; polarity reversal can lead to the digital outputs being connected through |
Input current |
from load voltage L+ (without load), max. | 10 mA; Per channel |
from backplane bus 3.3 V DC, max. | 10 mA |
Power loss |
Power loss, typ. | 0.8 W |
Address area |
Address space per module |
Address space per module, max. | 1 byte |
with packing | 4 bit |
Digital outputs |
Number of digital outputs | 4 |
Short-circuit protection | Yes |
Response threshold, typ. | 1 to 1.5 A |
Controlling a digital input | Yes |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Load resistance range |
lower limit | 48 Ω |
upper limit | 3 400 Ω |
Output voltage |
for signal "1", min. | L+ (-1 V) |
Output current |
for signal "1" rated value | 0.5 A |
for signal "1" permissible range, min. | 7 mA |
for signal "1" permissible range, max. | 600 mA |
for signal "0" residual current, max. | 0.3 mA |
Output delay with resistive load |
"0" to "1", max. | 45 µs; Typical value |
"1" to "0", max. | 90 µs; Typical value |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | Yes; per module |
Switching frequency |
with resistive load, max. | 800 Hz |
with inductive load, max. | 2 Hz |
on lamp load, max. | 10 Hz |
Total current of the outputs |
Current per module, max. | 2 A |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | Yes |
Interrupts/diagnostics/status information |
Diagnostics function | No |
Diagnostics indication LED |
Status indicator digital output (green) | Yes |
Parameter |
Remark | 1 byte |
Potential separation |
Potential separation digital outputs |
between the channels | No |
between the channels and backplane bus | Yes |
Isolation |
Isolation tested with | 500 V DC |
Ambient conditions |
Ambient temperature during operation |
min. | -25 °C; = Tmin |
max. | 70 °C; = Tmax |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 5 000 m |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
Use on ships/at sea |
— to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
— to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
Remark |
— Note regarding classification of environmental conditions acc. to EN 60721 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |
last modified: | 03/25/2019 |