6AG1131-4BF00-7AA0
SIPLUS ET200S EM 8 DI

From SIEMENS

SIPLUS ET 200S EM 8 DI -25...+70°C based on 6ES7131-4BF00-0AA0
Supply voltage
Rated value (DC)
24 V DCYes
Reverse polarity protectionYes
Input current
from supply voltage L+, max.Dependent on encoder
from backplane bus 3.3 V DC, max.10 mA
Encoder supply
Number of outputs0; no encoder supply
Power loss
Power loss, typ.1.2 W
Address area
Address space per module
Address space per module, max.1 byte
Digital inputs
Number of digital inputs8
Input characteristic curve in accordance with IEC 61131, type 1Yes; 2-wire sensors connectable
Number of simultaneously controllable inputs
Number of simultaneously controllable inputs8
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"-30 to +5V
for signal "1"+15 to +30V
Input current
for signal "1", typ.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableNo
— at "0" to "1", min.2 ms
— at "0" to "1", max.4.5 ms
— at "1" to "0", min.2 ms
— at "1" to "0", max.4.5 ms
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes; TWE = 3000 us
Interrupts/diagnostics/status information
Diagnostics functionNo
Diagnostics indication LED
Status indicator digital input (green)Yes
Parameter
Remark3-byte parameter (not accessible for the user)
Potential separation
Potential separation digital inputs
between the channelsNo
between the channels and backplane busYes
Permissible potential difference
between different circuits75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
Ambient conditions
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.35 g
last modified:03/13/2019