5SM3312-0LB
RCCB

From SIEMENS

Residual current operated circuit breaker, 2-pole, type AC, In: 25 A, 30 mA, Un AC: 230 V
Model
Product brand nameSENTRON
Product designationRCCB
Design of the productInstantaneous
General technical data
Number of poles2
Size of installation devices / acc. to DIN 438801
Protection against electrical shockFinger and back-of-hand safe
circuit-breaker / Design5SM3
Mechanical service life (switching cycles) / typical10 000
Switching function / short-term delayedNo
Overvoltage categoryIII
Supply voltage
Supply voltage
at AC / rated value230 V
for testing equipment / minimum195 V
Supply voltage frequency / rated value50 Hz
Protection class
Protection class IPIP20, if the distribution board is installed, with connected conductors
Switching capacity
Switching capacity current / according to IEC 61008-1 / rated value0.5 kA
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole2 W
Electricity
Tripping residual current / rated value30 mA
Type of fault currentAC
Current / at AC / rated value25 A
Surge current resistance / rated value1 kA
Operating frequency50Hz
Product details
Product feature / silicon-freeYes
Product extension / can be installed / supplementary devicesYes
Number
Number of test cycles / for environmental testing / acc. to IEC 60068-2-3028
Connections
Connectable conductor cross-section / stranded
minimum1 mm²
maximum16 mm²
Connectable conductor cross-section / solid
minimum1 mm²
maximum16 mm²
Tightening torque / with screw-type terminals
minimum2.5 N·m
maximum3 N·m
Position / of power supply cordtop or bottom
Mechanical Design
Height90 mm
Width36 mm
Depth70 mm
Mounting positionany
Installation depth70 mm
Number of width units2
Mounting typeDIN rail (REG)
Net weight244 g
Environmental conditions
Ambient temperature
minimum-5 °C
maximum45 °C
during storage / minimum permissible-40 °C
during storage / maximum permissible75 °C

External links