4BU5895-0UC55-2F
TR PN(KVA):130 UPRI(V):525 USEC(V):400

From SIEMENS

POWER TRANSFORMER; PHASES:3; PN(KVA):130; UPRI(V):525; USEC(V):400; ISEC(A):187,6; UK(%):3,4; F(HZ):50...60; VECTOR GR./SHIELD WNG.:DYN11 /0; TA/ISOKL:40 /H; IP23; TYPE OF TERMINALS:SCREW/FLAT-TYPE TERMINAL; INSTALLATION:SCREW; VDE 0532
General technical data:
Product designationpower transformer
Product brand nameSIDAC
Operating apparent output rated valueV·A130 000
Efficiency0.97
Connection method for transformersDyn11
Certificate of suitabilityCE
Product function
Temperature monitoringYes
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Relative short-circuit voltage%3.4
Inputs:
Phase number of the inputs3
Input voltage
_1 rated valueV525
Electrical input frequency
minimumHz50
maximumHz60
Outputs:
Phase number of the outputs3
Output voltage
_1 rated valueV400
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions:
Thermal class acc. to IEC 60085H
Ambient temperature rated value°C40
Protection class IPIP23
Mechanical data:
Type of electrical connection
at output for main current circuitflat connector / screw-type terminals
at input for main current circuitflat connector / screw-type terminals
Type of the temperature monitoringdeactivation
Mounting typescrews
Construction form of the iron core3UI 370/150

External links