4BU5895-0UC45-2F
POWER TRANSFORMER; PHASES:3;

From SIEMENS

POWER TRANSFORMER; PHASES:3; PN(KVA):130; UPRI(V):525; USEC(V):400; ISEC(A):187,6; UK(%):3,4; F(HZ):50...60; VECTOR GR./SHIELD WNG.:DYN11 /0; TA/ISOKL:45 /H; IP23; TYPE OF TERMINALS:FLAT-TYPE TERMINAL; INSTALLATION:SCREW; VDE 0532
General technical data:
Product designationpower transformer
Product brand nameSIDAC
Operating apparent output rated valueV·A130 000
Connection method for transformersDyn11
Certificate of suitabilityCE
Product function
Temperature monitoringYes
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Relative short-circuit voltage%3.4
Inputs:
Phase number of the inputs3
Input voltage
_1 rated valueV525
Electrical input frequency
minimumHz50
maximumHz60
Outputs:
Phase number of the outputs3
Output voltage
_1 rated valueV400
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions:
Thermal class acc. to IEC 60085H
Ambient temperature rated value°C45
Protection class IPIP23
Mechanical data:
Type of electrical connection
at output for main current circuitflat connector
at input for main current circuitflat connector
Type of the temperature monitoringdeactivation
Mounting typescrews
Construction form of the iron core3UI 370/150

External links