4BU5842-5AR10-2DB0
TRANSFORMER PHASES:3

From SIEMENS

TRANSFORMER; PHASES:3; PN(KVA):125; UPRI(V):400+/-5%; USEC(V):208; ISEC(A):347; F(HZ):50...60; VECTOR GR./SHIELD WNG.:DYN5 /0; TA/ISOKL:40 /H; IP20; TYPE OF TERMINALS:FLAT-TYPE TERMINAL; INSTALLATION:PLACE; VDE 0532
General technical data:
Product designationtransformer
Product brand nameSIDAC
Operating apparent output rated valueV·A125 000
Efficiency0.95
Connection method for transformersDyn5
Certificate of suitabilityCE
Product function
Temperature monitoringNo
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Inputs:
Phase number of the inputs3
Input voltage
_1 rated valueV420
_2 rated valueV400
_3 rated valueV380
Electrical input frequency
minimumHz50
maximumHz60
Outputs:
Phase number of the outputs3
Output voltage
_1 rated valueV208
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions:
Thermal class acc. to IEC 60085H
Ambient temperature rated value°C40
Protection class IPIP20
Mechanical data:
Type of electrical connection
at output for main current circuitflat connector
at input for main current circuitflat connector
Mounting typeinstallation
Construction form of the iron core3UIS 395/150
Widthm1.22
Heightm0.905
Depthm0.73

External links