4AU3696-0CG40-2CA0 TRTRAFO PN(KVA):7 UPRI(V):480 USEC(V)400
From SIEMENS
ISOLATION TRANSFORMER; PHASES:3; PN(KVA):7; UPRI(V):480; USEC(V):400; ISEC(A):10,1; F(HZ):50...60; VECTOR GR./SHIELD WNG.:YYN0 /0; TA/ISOKL:55 /H; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; EN 61558-2-4 >UL/CSA-RECOGNIZED< >ISOLATION TRANSFORMER< | |||
General technical data | |||
Product designation | isolation transformer | ||
Product brand name | SIDAC | ||
Operating apparent output rated value | V·A | 7 000 | |
Efficiency | 0.94 | ||
Connection method for transformers | Yyn0 | ||
Certificate of suitability | CE / cRUus | ||
Product function | |||
Temperature monitoring | No | ||
Insulation monitoring | No | ||
Short-circuit and overload proof | No | ||
Number of shielding windings | 0 | ||
Relative short-circuit voltage | % | 5.28 | |
Inputs | |||
Phase number of the inputs | 3 | ||
Input voltage | |||
_1 rated value | V | 480 | |
Electrical input frequency | |||
minimum | Hz | 50 | |
maximum | Hz | 60 | |
Outputs | |||
Phase number of the outputs | 3 | ||
Output voltage | |||
_1 rated value | V | 400 | |
Electrical output frequency | |||
maximum | Hz | 60 | |
minimum | Hz | 50 | |
Ambient conditions | |||
Thermal class acc. to IEC 60085 | H | ||
Ambient temperature rated value | °C | 55 | |
Protection class IP | IP00 | ||
Mechanical data | |||
Type of electrical connection | |||
at output for main current circuit | screw-type terminals | ||
at input for main current circuit | screw-type terminals | ||
Mounting type | screws | ||
Construction form of the iron core | 3UI 180/75 | ||
Width | m | 0.36 | |
Height | m | 0.32 | |
Depth | m | 0.268 | |
Certificates/ approvals |