4AU3696-0CG40-2CA0
TRTRAFO PN(KVA):7 UPRI(V):480 USEC(V)400

From SIEMENS

ISOLATION TRANSFORMER; PHASES:3; PN(KVA):7; UPRI(V):480; USEC(V):400; ISEC(A):10,1; F(HZ):50...60; VECTOR GR./SHIELD WNG.:YYN0 /0; TA/ISOKL:55 /H; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; EN 61558-2-4 >UL/CSA-RECOGNIZED< >ISOLATION TRANSFORMER<
General technical data
Product designationisolation transformer
Product brand nameSIDAC
Operating apparent output rated valueV·A7 000
Efficiency0.94
Connection method for transformersYyn0
Certificate of suitabilityCE / cRUus
Product function
Temperature monitoringNo
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Relative short-circuit voltage%5.28
Inputs
Phase number of the inputs3
Input voltage
_1 rated valueV480
Electrical input frequency
minimumHz50
maximumHz60
Outputs
Phase number of the outputs3
Output voltage
_1 rated valueV400
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions
Thermal class acc. to IEC 60085H
Ambient temperature rated value°C55
Protection class IPIP00
Mechanical data
Type of electrical connection
at output for main current circuitscrew-type terminals
at input for main current circuitscrew-type terminals
Mounting typescrews
Construction form of the iron core3UI 180/75
Widthm0.36
Heightm0.32
Depthm0.268
Certificates/ approvals

External links