4AU3032-8CC40-0HC0
3-PH. SITAS-TRANSFORMER

From SIEMENS

TRANSFORMER SITAS; PHASES:3; PN/PN(S6)(KVA):5 /28; UPRI(V):Y500-440-380+/-20/D289- 254-220+/-11; USEC(V):Y 400 / D 230; ISEC(A):7,2-12,5; F(HZ):50...60; VECTOR GR./SHIELD WNG.:IIIIII0 /0; TA/ISOKL:55 /H; IP23; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; EN 61558-2-1, -2-2, -2-4 >UL/CSA-RECOGNIZED< >CONTROL CIRCUIT TRANSFORMER< >ISOLATION TRANSFORMER<
General technical data
Product designationtransformer SITAS
Product brand nameSIDAC
Operating apparent output rated valueV·A5 000
Efficiency0.96
Connection method for transformersIIIiii0
Certificate of suitabilityCE / cRUus
Product function
Temperature monitoringNo
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Short-term vector powerV·A28 000
Relative short-circuit voltage%2.6
Inputs
Phase number of the inputs3
Input voltage
_1 rated valueV520
_2 rated valueV500
_3 rated valueV480
_4 rated valueV460
_5 rated valueV440
_6 rated valueV420
_7 rated valueV400
_8 rated valueV380
_9 rated valueV360
_10 rated valueV300
_11 rated valueV289
_12 rated valueV277
_13 rated valueV266
_14 rated valueV254
_15 rated valueV240
_16 rated valueV230
Electrical input frequency
minimumHz50
maximumHz60
Outputs
Phase number of the outputs3
Output voltage
_1 rated valueV400
_2 rated valueV230
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions
Thermal class acc. to IEC 60085H
Ambient temperature rated value°C55
Protection class IPIP23
Mechanical data
Type of electrical connection
at output for main current circuitscrew-type terminals
at input for main current circuitscrew-type terminals
Mounting typescrews
Construction form of the iron core3UI 150/75
Widthm0.351
Heightm0.395
Depthm0.33
Certificates/ approvals

External links