4AT3096-0AV40-0CA0 CONTROL CIRCUIT TRANSFORMER;
From SIEMENS
CONTROL CIRCUIT TRANSFORMER; PHASES:1; PN/PN(S6)(KVA):4 /18,1; UPRI(V):240+/-5%+/-10%; USEC(V):110; ISEC(A):36,4; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:55 /H; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; EN 61558-2-2 >UL/CSA-RECOGNIZED< >CONTROL CIRCUIT TRANSFORMER< | |||
General technical data: | |||
Product designation | control circuit transformer | ||
Product brand name | SIDAC | ||
Operating apparent output rated value | V·A | 4 000 | |
Efficiency | 0.95 | ||
Connection method for transformers | Ii0 | ||
Certificate of suitability | CE / cRUus | ||
Product function | |||
Temperature monitoring | No | ||
Insulation monitoring | No | ||
Short-circuit and overload proof | No | ||
Number of shielding windings | 0 | ||
Short-term vector power | V·A | 18 100 | |
Relative short-circuit voltage | % | 3.56 | |
Inputs: | |||
Phase number of the inputs | 1 | ||
Input voltage | |||
_1 rated value | V | 264 | |
_2 rated value | V | 252 | |
_3 rated value | V | 240 | |
_4 rated value | V | 228 | |
_5 rated value | V | 216 | |
Electrical input frequency | |||
minimum | Hz | 50 | |
maximum | Hz | 60 | |
Outputs: | |||
Phase number of the outputs | 1 | ||
Output voltage | |||
_1 rated value | V | 110 | |
Electrical output frequency | |||
maximum | Hz | 60 | |
minimum | Hz | 50 | |
Ambient conditions: | |||
Thermal class acc. to IEC 60085 | H | ||
Ambient temperature rated value | °C | 55 | |
Protection class IP | IP00 | ||
Mechanical data: | |||
Type of electrical connection | |||
at output for main current circuit | screw-type terminals | ||
at input for main current circuit | screw-type terminals | ||
Mounting type | screws | ||
Construction form of the iron core | UI 150/75 | ||
Width | m | 0.164 | |
Height | m | 0.27 | |
Depth | m | 0.155 |