4AM4842-1TB50-0AA0
AUT TRANS PHA1 PN,D(KVA):1,6 UPRI(V):230

From SIEMENS

AUTOTRANSFORMER; PHASES:1; PN,D(KVA):1,6; UPRI(V):230; USEC(V):190-175-150-125-100-80; ISEC(A):8,421 CONST.; F(HZ):50...60; VECTOR GR./SHIELD WNG.:IA0 /0; TA/ISOKL:50 /B; IP00; TYPE OF TERMINALS:SCREW/TAB CONNECTION; INSTALLATION:SCREW; EN 61558-2-13 >UL/CSA-RECOGNIZED< >AUTOTRANSFORMER<
General technical data:
Product designationautotransformer
Product brand nameSIDAC
Operating apparent output rated valueV·A1 600
Efficiency0.91
Connection method for transformersIa0
Certificate of suitabilityCE / cRUus
Product function
Temperature monitoringNo
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Inputs:
Phase number of the inputs1
Input voltage
_1 rated valueV230
Electrical input frequency
minimumHz50
maximumHz60
Outputs:
Phase number of the outputs1
Output voltage
_1 rated valueV190
_2 rated valueV175
_3 rated valueV150
_4 rated valueV125
_5 rated valueV100
_6 rated valueV80
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions:
Thermal class acc. to IEC 60085B
Ambient temperature rated value°C50
Protection class IPIP00
Mechanical data:
Type of electrical connection
at output for main current circuitscrew-type terminals / tab terminals
at input for main current circuitscrew-type terminals / tab terminals
Mounting typescrews
Construction form of the iron coreEI 120/72
Widthm0.122
Heightm0.121
Depthm0.134

External links