3VA2225-5JP32-0AA0
MCCB_IEC_FS250_250A_3P_55KA_ETU5_LSI

From SIEMENS

circuit breaker 3VA2 IEC frame 250 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection ETU550, LSI, In=250A overload protection Ir=100A...250A short-circuit protection Isd=0.6..10x In, Ii=1.5..10x In N conductor protection optionally with external current transformer, up to 160% nut keeper kit
Model
Product brand nameSENTRON
Product designationMolded case circuit breaker
Product versionLine protection
Design of the overcurrent releaseETU550
Protective function of the overcurrent releaseLSI
Number of poles3
General technical data
Rated insulation voltage Ui800 V
Max. rated operational voltage Ue with AC 50/60Hz690 V
Power loss [W] / maximum48 W
Active power loss / for rated value of the current / at AC / in hot operating state / per pole16 W
Latching - endurance20 000
Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz10 000
Electrical endurance (switching cycles) / at AC-1 / at 690 V 50/60 Hz5 000
Neutral conductors / upgradeable/retrofittableYes
Ground fault monitoring versionWithout
Product function
communication functionYes
other measurement functionNo
Net weight2.25 kg
Electricity
Max. rated operational voltage of the size of the circuit-breaker250 A
Rated continuous current Iu250 A
Operating current
at 40 °C250 A
at 45 °C250 A
at 50 °C250 A
at 55 °C238 A
at 60 °C225 A
at 65 °C213 A
at 70 °C200 A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breakerM
Maximum short-circuit current breaking capacity (Icu)
at 240 V85 kA
at 415 V55 kA
at 440 V55 kA
at 500 V36 kA
at 690 V3 kA
Operational short-circuit current breaking capacity (Ics)
at 240 V85 kA
at 415 V55 kA
at 440 V55 kA
at 500 V36 kA
at 690 V3 kA
Short-circuit current making capacity (Icm)
at 240 V187 kA
at 415 V121 kA
at 440 V121 kA
at 500 V76 kA
at 690 V4.5 kA
Adjustable parameters
Adjustable response value current / lr min.100 A
Adjustable response value current / Ir max.250 A
Adjustable response value time / tr min.0.5
Adjustable response value time / tr max.15
Adjustable response value current / Isd min.150 A
Adjustable response value current / Isd max.2 500 A
Short-term delayed / tripping switchable / I2t=ON/OFFYes
Adjustable response value time / tsd min.0.05 s
Adjustable response value time / tsd max.0.5 s
Adjustable response value time / tsd min.0.05 s
Adjustable response value time / tsd max.0.5 s
Adjustable response value current / li min.375 A
Adjustable response value current / li max.2 500 A
Design of the N-conductor protectionWithout
Ground fault protection / tripping switchable / I2t=ON/OFFNo
Mechanical Design
Height [in]7.1 in
Height181 mm
Width [in]4.1 in
Width105 mm
Depth [in]3.4 in
Depth86 mm
Connections
Arrangement of electrical connectors / for main current circuitFront terminal
Type of electrical connection / for main current circuitLug terminal
Type of connectable conductor cross-section, connection screw, width x thickness , min.13 x 1 mm
Type of connectable conductor cross-section, connection screw, width x thickness , max.25 x 8.5
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Accessories
Product extension / optional / motor driveYes
Environmental conditions
Protection class IP / on the frontIP40
Ambient temperature
during operation / minimum-25 °C
during operation / maximum70 °C
during storage / minimum-40 °C
during storage / maximum80 °C