3VA1225-4EF42-0AA0
MCCB_IEC_FS250_250A_4P_36KA_TM_ ATAM

From SIEMENS

circuit breaker 3VA1 IEC frame 250 breaking capacity class S Icu=36kA @ 415V 4-pole, line protection TM240, ATAM, In=250A overload protection Ir=175A...250A short-circuit protection Ii=5...10 x In N conductor unprotected nut keeper kit
Model
Product brand nameSENTRON
Product designationMolded case circuit breaker
Product versionLine protection
Design of the overcurrent releaseTM240
Protective function of the overcurrent releaseLI
Number of poles4
General technical data
Rated insulation voltage Ui800 V
Max. rated operational voltage Ue with AC 50/60Hz690 V
Max. rated operational voltage Ue with DC600 V
Power loss [W] / maximum57 W
Active power loss / for rated value of the current / at AC / in hot operating state / per pole19 W
Latching - endurance15 000
Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz8 000
Electrical endurance (switching cycles) / at AC-1 / at 690 V 50/60 Hz5 000
Neutral conductors / upgradeable/retrofittableNo
Ground fault monitoring versionWithout
Product function
communication functionNo
other measurement functionNo
Net weight2.099 kg
Electricity
Max. rated operational voltage of the size of the circuit-breaker250 A
Rated continuous current Iu250 A
Operating current
at 40 °C250 A
at 45 °C250 A
at 50 °C250 A
at 55 °C243.3 A
at 60 °C236.5 A
at 65 °C229.8 A
at 70 °C223 A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breakerS
Maximum short-circuit current breaking capacity (Icu)
at 240 V55 kA
at 415 V36 kA
at 440 V25 kA
at 690 V7 kA
Operational short-circuit current breaking capacity (Ics)
at 240 V55 kA
at 415 V36 kA
at 440 V25 kA
at 690 V5 kA
Short-circuit current making capacity (Icm)
at 240 V121 kA
at 415 V76 kA
at 440 V53 kA
at 690 V11.9 kA
Adjustable parameters
Adjustable response value current / lr min.175 A
Adjustable response value current / Ir max.250 A
Short-term delayed / tripping switchable / I2t=ON/OFFNo
Adjustable response value current / li min.1 250 A
Adjustable response value current / li max.2 500 A
Design of the N-conductor protectionWithout
Ground fault protection / tripping switchable / I2t=ON/OFFNo
Mechanical Design
Height [in]6.2 in
Height158 mm
Width [in]5.5 in
Width140 mm
Depth [in]2.8 in
Depth70 mm
Connections
Arrangement of electrical connectors / for main current circuitFront terminal
Type of electrical connection / for main current circuitlug terminal
Type of connectable conductor cross-section, connection screw, width x thickness , min.13 x 1
Type of connectable conductor cross-section, connection screw, width x thickness , max.25 x 8
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Accessories
Product extension / optional / motor driveYes
Environmental conditions
Protection class IP / on the frontIP40
Ambient temperature
during operation / minimum-25 °C
during operation / maximum70 °C
during storage / minimum-40 °C
during storage / maximum80 °C

External links