| 22MM METAL ROUND COMPLETE UNIT COMBINATION: EMERGEN.-STOP MUSHR.PUSHB. 40MM LATCH.W. ROT.-TO-UNLATCH MECH. WITH YELLOW BACKING PLATE SPRING-LOADED TERMINAL, 1NC WITH HOLDER RED INSCRIPTION: NOT-HALT !!! Phased-out product !!! SIRIUS ACT 3SU1 is suc Preferred successor ty >>3SU1150-1HB20-3CH0 << |
Design of the product | Complete unit round with positive latching in accordance with ISO 13850 |
Enclosure |
Shape of the enclosure front | round |
Material of the enclosure | metal |
Number of command points | 1 |
Actuator |
Design of the operating mechanism | Emergency stop mushroom pushbutton |
Manner of function of the actuating element | Latching |
Product extension optional Light source | No |
Color | |
of the actuating element | Red |
Material of the actuating element | plastic |
Type of unlocking device | rotate-to-unlatch mechanism |
Number of switching positions | 2 |
Front ring |
Product component front ring | No |
Holder |
Material of the holder | Metal |
Contact block/ lampholder |
Number of lampholders | 0 |
Number of switching elements | 1 |
General technical data |
Product function | |
positive opening | Yes |
Product component | |
Light source | No |
Type of voltage | |
of the operating voltage | AC/DC |
Protection class IP | IP67 |
Operating frequency maximum | 1 000 1/h |
Mechanical service life (switching cycles) | |
typical | 300 000 |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | S |
Reference code acc. to DIN EN 81346-2 | S |
Reference code acc. to DIN EN 61346-2 | S |
Operating voltage | |
rated value | 5 ... 400 V |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | 1 |
Number of NO contacts for auxiliary contacts | 0 |
Number of CO contacts | |
for auxiliary contacts | 0 |
Operating current at AC-12 | |
at 24 V rated value | 10 A |
at 48 V rated value | 10 A |
at 110 V rated value | 10 A |
at 230 V rated value | 10 A |
at 400 V rated value | 10 A |
Operating current at AC-15 | |
at 24 V rated value | 6 A |
at 48 V rated value | 6 A |
at 110 V rated value | 6 A |
at 230 V rated value | 6 A |
at 400 V rated value | 3 A |
Operating current at DC-12 | |
at 24 V rated value | 10 A |
at 48 V rated value | 5 A |
at 110 V rated value | 2.5 A |
at 230 V rated value | 1 A |
Operating current at DC-13 | |
at 24 V rated value | 3 A |
at 48 V rated value | 1.5 A |
at 110 V rated value | 0.7 A |
at 230 V rated value | 0.3 A |
Connections/Terminals |
Type of electrical connection | spring-loaded terminals |
Tightening torque of the screws in the bracket | 1.4 ... 1.6 N·m |
Safety related data |
B10 value | |
with high demand rate acc. to SN 31920 | 100 000 |
Proportion of dangerous failures | |
with low demand rate acc. to SN 31920 | 20 % |
with high demand rate acc. to SN 31920 | 20 % |
Failure rate [FIT] | |
with low demand rate acc. to SN 31920 | 100 FIT |
T1 value for proof test interval or service life acc. to IEC 61508 | 20 y |
Ambient conditions |
Ambient temperature | |
during operation | -25 ... +70 °C |
during storage | -40 ... +80 °C |
Environmental category during operation acc. to IEC 60721 | 3K6 |
Installation/ mounting/ dimensions |
Mounting type | front mounting |
Shape of the installation opening | round |
Mounting diameter | 22 mm |
Mounting height | 49 mm |
Installation width | 40.5 mm |
Installation depth | 50 mm |
Accessories |
Product component holder for 3 switching elements | No |