| AS-i Power 5A 120 V/230 V AC AS-Interface power supply unit, IP20 IN: 120 V / 230 V AC OUT: AS-i, 5 A (30 V DC), IP20 with integrated ground fault detection, with integrated overload detection with AS-i data decoupling |
General technical data: |
Type of device | | AS-Interface power supply unit IP20 |
version | | single output |
input voltage nominal value AC | | |
range 1 | V | 120 |
range 2 | V | 230 |
Additional function | | integrated ground-fault detection, remote reset and remote indication |
Inputs: |
input recommended circuit breaker (IEC 898) in the main supply line | | 6 A, characteristic C |
input voltage range | | |
voltage range 1 AC | V | 85 ... 132 |
voltage range 2 AC | V | 176 ... 253 |
input | | |
Mains buffering time at Ia rated min | | 20 ms |
line frequency | | 50/60 Hz |
Mains frequency range | Hz | 47 ... 63 |
range changeover using | | Changeover switch on device |
input voltage built-in | | T 3.15 (not accessible) |
Connections input | | spring-loaded terminal connection input (0.2 ... 2.5 mm2)/ diagnosis (0.14 ... 1.5 mm2) |
Outputs: |
output | | |
DC-voltage controlled floating according to AS-Interface spezification | | yes |
voltage rated value Ua rated DC | | 30 V |
tolerance total DC | V | 29.5 ... 31.6 |
rated current Ia rated | | 5 A |
residual ripple peak-to-peak ( 0-10 kHz, AS-i+/AS-i- ) max | mV | 300 |
spikes peak-to-peak ( 10-500 kHz, AS-i+/AS-i- ) max | mV | 50 |
Connections Output | | spring-loaded terminal connection output (0.2 ... 2.5 mm²)/ diagnosis (0.14 ... 1.5 mm²) |
Efficiency/ heat loss: |
Efficiency at Ua rated, Ia rated | % | 87 |
Protective and monitoring functions: |
Output overvoltage protection | | yes (< 35V) |
Current limitation from min. | | 5.5 A |
Short-circuit protection | | yes |
Safety related data: |
protection class ( EN 60 950/IEC 950 ) | | I |
Electrical isolation primary/secondary | | SELV according to EN 60 950 and EN 50 178 |
Protection class IP | | IP20 |
Electromagnetic compatibility: |
electromagnetic compatibility (EMC) | | |
interference immunity | | EN 61 000-6-2, EN 61 000-4-2/-3/-4/-5/-11 |
emitted interference | | class B according to EN 55 022, IEC 61 000-6-3 |
Ambient conditions: |
Ambient temperature | | |
during operation | °C | -10 ... +70 |
during storage | °C | -25 ... +80 |
humidity rating | | climatic class DIN 50010, relative humidity max. 100% without condensation |
Mounting type | | fixing on standard mounting rail DIN EN 59 022-35 x 7.5 mm snap-on |
Width | mm | 70 |
Height | mm | 125 |
Depth | mm | 125 |