3RX9307-1AA00
As-interf. power supply unit 4A, NPUT voltage 115V, 230V AC; primary CLOCKING

From SIEMENS

AS-INTERF. POWER SUPPLY UNIT 4 A, NPUT VOLTAGE 115V,230 V AC SWITCHABLE, PRIMARY CLOCKING
General technical data:
Type of deviceAS-Interface power supply unit IP20
versionsingle output
input voltage nominal value AC
range 1V115
range 2V230
Inputs:
input recommended circuit breaker (IEC 898) in the main supply line10 A and higher, characteristic C
input voltage range
voltage range 1 ACV102 ... 132
voltage range 2 ACV195 ... 253
input
Mains buffering time at Ia rated min20 ms
line frequency50/60 Hz
Mains frequency rangeHz47 ... 63
range changeover usingChangeover switch on device
input voltage built-inT 5 (not accessible)
Connections inputspring-loaded terminal connection (0.8 ... 2.5 mm2)
Outputs:
output
DC-voltage controlled floating according to AS-Interface spezificationyes
voltage rated value Ua rated DC30 V
tolerance total DCV29.5 ... 31.6
rated current Ia rated4 A
residual ripple peak-to-peak ( 0-10 kHz, AS-i+/AS-i- ) maxmV300
spikes peak-to-peak ( 10-500 kHz, AS-i+/AS-i- ) maxmV50
Connections Outputspring-loaded terminal connection (0.8 ... 2.5 mm²)
Efficiency/ heat loss:
Efficiency at Ua rated, Ia rated%85
Protective and monitoring functions:
Output overvoltage protectionno
Current limitation from min.4.5 A
Short-circuit protectionyes
Safety related data:
protection class ( EN 60 950/IEC 950 )I
Electrical isolation primary/secondarySELV according to EN 60 950 (available soon)
Protection class IPIP20
Electromagnetic compatibility:
electromagnetic compatibility (EMC)
interference immunityEN 50 082-2
emitted interferenceEN 50 081-1
Ambient conditions:
Ambient temperature
during operation°C-25 ... +55
during storage°C-25 ... +60
humidity ratingmax. 80% rel. Humidity
Mounting typefixing on standard mounting rail DIN EN 50 022-35 x 7.5 mm snap-on
Widthmm75
Heightmm135
Depthmm107

External links