3RV1342-4BC10
CIRCUIT-BREAKER, SIZE S3,

From SIEMENS

Circuit breaker size S3 For starter combination Rated current 20 A Short-circuit release 260 A Screw terminal Increased switching capacity !!! Phased-out product !!! Successor is SIRIUS 3RV2 Preferred successor type is >>3RV2332-4BC10<<
Product brand nameSIRIUS
Product designationcircuit breaker
Design of the productfor starter combinations
General technical data
Product extension
Auxiliary switchYes
Power loss [W] total typical20 W
Surge voltage resistance rated value6 000 V
Protection class IP
on the frontIP20
Shock resistance25g / 11 ms
Mechanical service life (switching cycles)
of the main contacts typical50 000
Continuous current rated value20 A
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Ambient temperature
during operation-20 ... +60 °C
during storage-50 ... +80 °C
during transport-50 ... +80 °C
Main circuit
Number of poles for main current circuit3
Operating voltage
rated value690 V
at AC-3 rated value maximum690 V
Operating current
at AC-3
— at 400 V rated value20 A
Operating power
at AC-3
— at 400 V rated value7.5 kW
Operating frequency
at AC-3 maximum15 1/h
Auxiliary circuit
Number of CO contacts
for auxiliary contacts0
Protective and monitoring functions
Product function
Ground fault detectionNo
Phase failure detectionNo
Maximum short-circuit current breaking capacity (Icu)
at AC at 240 V rated value100 kA
at AC at 400 V rated value100 kA
at AC at 500 V rated value30 kA
at AC at 690 V rated value12 kA
Short-circuit protection
Design of the overcurrent release and short-circuit releasemagnetic
Installation/ mounting/ dimensions
Mounting positionany
Mounting typescrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Height165 mm
Width70 mm
Depth174 mm
Required spacing
with side-by-side mounting
— Backwards0 mm
— at the side0 mm
Connections/Terminals
Product function
removable terminal for auxiliary and control circuitNo
Type of electrical connection
for main current circuitscrew-type terminals with box terminals
for auxiliary and control current circuitscrew-type terminals
Arrangement of electrical connectors for main current circuitfront side
Type of connectable conductor cross-sections
for main contacts
— solid2x (2.5 ... 16 mm²)
— stranded2x (10 ... 50 mm²), 1x (10 ... 70 mm²)
— finely stranded with core end processing2x (2.5 ... 35 mm²), 2.5 ... 50 mm²
at AWG conductors for main contacts2x (10 ... 1), 1x (10 ... 2)

External links