| Special type Circuit breaker size S2 for motor protection; Class 20 A-release 22...32 A Short-circuit release 416 A Screw terminal Standard switching capacity Ambient temperature -50 °C 500 switching cycles !!! Phased-out product !!! Successor is SIRIUS 3RV2 Preferred successor type is >>3RV2031-4EB10-0BA0<< |
Product brand name | SIRIUS |
Product designation | circuit breaker |
Design of the product | for motor protection |
General technical data |
Product extension | |
Auxiliary switch | Yes |
Power loss [W] total typical | 15 W |
Surge voltage resistance rated value | 6 000 V |
Protection class IP | |
on the front | IP20 |
Shock resistance | 25g / 11 ms |
Mechanical service life (switching cycles) | |
of the main contacts typical | 500 |
Continuous current rated value | 32 A |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Main circuit |
Number of poles for main current circuit | 3 |
Adjustable pick-up value current of the current-dependent overload release | 22 ... 32 A |
Operating voltage | |
rated value | 690 V |
at AC-3 rated value maximum | 690 V |
Operating current | |
at AC-3 | |
— at 400 V rated value | 32 A |
Operating power | |
at AC-3 | |
— at 400 V rated value | 15 kW |
Operating frequency | |
at AC-3 maximum | 15 1/h |
Auxiliary circuit |
Number of CO contacts | |
for auxiliary contacts | 0 |
Protective and monitoring functions |
Product function | |
Ground fault detection | No |
Phase failure detection | Yes |
Trip class | Class 20 |
Maximum short-circuit current breaking capacity (Icu) | |
at AC at 240 V rated value | 100 kA |
at AC at 400 V rated value | 50 kA |
at AC at 500 V rated value | 10 kA |
at AC at 690 V rated value | 4 kA |
Short-circuit protection |
Design of the overcurrent release and short-circuit release | thermomagnetic |
Installation/ mounting/ dimensions |
Mounting position | any |
| |
(mounting type) | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
Height | 140 mm |
Width | 55 mm |
Depth | 149 mm |
Required spacing | |
with side-by-side mounting | |
— Backwards | 0 mm |
— at the side | 0 mm |
Connections/Terminals |
Product function | |
removable terminal for auxiliary and control circuit | No |
Type of electrical connection | |
for main current circuit | screw-type terminals with box terminals |
for auxiliary and control current circuit | screw-type terminals |
Arrangement of electrical connectors for main current circuit | front side |
Type of connectable conductor cross-sections | |
for main contacts | |
— solid | 2x (0.75 ... 16 mm²) |
— stranded | 2x (0.75 ... 25 mm²), 1x (0.75 … 35 mm²) |
— finely stranded with core end processing | 2x (0.75 ... 16 mm²), 0.75 ... 25 mm² |
at AWG conductors for main contacts | 2x (18 ... 2), 1x (18 ... 2) |