3RK1408-8KG00-0AA2 AS-INTERFACE SLIMLINE MODULE
From SIEMENS
AS-i ground fault module IP20 S22.5, ground fault monitoring 1 input, remote reset 2 x signaling output, Relay DC-12 1 A / DC-13 500 mA (24 V) Spring-type terminal Overall width 22.5 mm No AS-i address required Only AS-Interface monitoring | |||
General technical data: | |||
Design of the product | ground-fault detection modules - modules with special functions | ||
Product function | |||
Ground fault detection | Yes | ||
counter | No | ||
Overvoltage detection | No | ||
Protocol is supported AS-interface protocol | Yes | ||
Type of electrical connection of the inputs and outputs | spring-loaded terminals | ||
AS interface total current input max | mA | 40 | |
Earth fault | 10% Uas-i <= Ugnd <= 90% Uas-i | ||
Addressing | the module does not need its own AS-Interface address | ||
Signal range | |||
low signal lin max | mA | 1.5 | |
high signal | |||
— Uin min | V | 10 | |
— lin min | mA | 6 | |
Current carrying capacity | |||
DC-12 | A | 1 | |
DC-13 | |||
— 24 V | mA | 500 | |
— 48 V | mA | 200 | |
Operating cycles DC-12 | 2 000 000 | ||
Rated operational voltage DC | V | 24 ... 48 | |
Rated temperature | °C | 25 | |
AS interface Connection Polarity reversal protection | built-in | ||
Note 1 | If repeaters are used, a ground fault detection module must be used for each AS-Interface segment (number of AS-Interface power supply units = number of ground fault detection modules) | ||
Note 2 | Uaux should be protected by a 2 A slow fuse. The endurance of the relay can be increased if inductive loads are connected using freewheel diodes. | ||
Equipment marking acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | A | ||
Equipment marking acc. to DIN EN 61346-2 | K | ||
Ambient conditions: | |||
Ambient temperature | |||
during operation | °C | -25 ... +70 | |
during storage | °C | -40 ... +85 | |
Protection class IP | IP20 | ||
Mechanical data: | |||
Width | mm | 22.5 | |
Height | mm | 103 | |
Depth | mm | 86 | |
Mounting type | standard rail mounting/wall mounting | ||
Conductor cross-section | |||
solid | 2 x (0.25 - 1.5) mm² | ||
finely stranded | |||
— with end sleeve | 2 x (0,25 - 1) mm² | ||
— without end sleeve | 2 x (0.25 - 1.5) mm² | ||
AWG solid or stranded | AWG 2 x (24 - 16) mm² |