| DS1E-X for ET200S High Feature DOL starter Setting range 0.3...3 A Mechanical switching Electronic protection AC-3, up to 1.1 kW / 400 V expandable for brake control module 2DI module Motor starter ES Circuit breaker signaling parameterizable |
Product brand name | SIMATIC |
Product designation | Motor starters |
Design of the product | direct starter |
Product type designation | ET 200S |
General technical data |
Product function | |
on-site operation | Yes |
Power loss [W] typical | 9 W |
Insulation voltage | |
rated value | 500 V |
Degree of pollution | 3 at 400 V, 2 at 500 V according to IEC60664 (IEC61131) |
Surge voltage resistance rated value | 6 kV |
maximum permissible voltage for safe isolation | |
between main and auxiliary circuit | 400 V |
Protection class IP | IP20 |
Shock resistance | 5g / 11 ms |
Operating frequency maximum | 750 1/h |
Mechanical service life (switching cycles) | |
of the main contacts typical | 100 000 |
Type of assignment | 2 |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | A |
Reference code acc. to DIN EN 81346-2 | Q |
Reference code acc. to DIN EN 61346-2 | Q |
Product function | |
direct start | Yes |
reverse starting | No |
Product component Motor brake output | Yes |
Product feature | |
brake control with 230 V AC | No |
brake control with 24 V DC | No |
brake control with 180 V DC | No |
brake control with 500 V DC | No |
Product extension braking module for brake control | Yes |
Product function Short circuit protection | Yes |
Design of short-circuit protection | circuit-breakers |
Trip class | CLASS 10 and 20 adjustable |
Maximum short-circuit current breaking capacity (Icu) | |
at 400 V rated value | 50 kA |
Electromagnetic compatibility |
EMC emitted interference | |
acc. to IEC 60947-1 | CISPR11, ambience A (industrial sector) |
EMI immunity acc. to IEC 60947-1 | corresponds to degree of severity 3, ambience A (industrial sector) |
Conducted interference | |
due to burst acc. to IEC 61000-4-4 | 2 kV on voltage supply, inputs and outputs |
due to conductor-earth surge acc. to IEC 61000-4-5 | 2 kV (U > 24 V DC) |
due to conductor-conductor surge acc. to IEC 61000-4-5 | 1 kV (U > 24 V DC) |
Field-bound parasitic coupling acc. to IEC 61000-4-3 | 80 MHz ... 1 GHz 10 V/m, 1.4 GHz ...2 Hz 3 V/m, 2 GHz ... 2.7 GHz 1 V/m |
Safety related data |
B10 value | |
with high demand rate acc. to SN 31920 | 1 000 000 |
Proportion of dangerous failures | |
with low demand rate acc. to SN 31920 | 50 % |
with high demand rate acc. to SN 31920 | 75 % |
Failure rate [FIT] | |
with low demand rate acc. to SN 31920 | 100 FIT |
T1 value for proof test interval or service life acc. to IEC 61508 | 20 y |
Protection against electrical shock | finger-safe |
Main circuit |
Number of poles for main current circuit | 3 |
Design of the switching contact | electromechanical |
Adjustable pick-up value current of the current-dependent overload release | 0.3 ... 3 A |
Type of the motor protection | solid-state |
Operating voltage | |
rated value | 200 ... 400 V |
Operating frequency 1 rated value | 50 Hz |
Operating frequency 2 rated value | 60 Hz |
Relative positive tolerance of the operating frequency | 10 % |
Relative negative tolerance of the operating frequency | 10 % |
Operating range relative to the operating voltage at AC | |
at 50 Hz | 200 ... 440 V |
Operating power | |
at AC-3 | |
— at 400 V rated value | 1.1 kW |
Inputs/ Outputs |
Product function | |
digital inputs parameterizable | Yes |
digital outputs parameterizable | No |
Number of digital inputs | 2 |
Number of sockets | |
for digital output signals | 0 |
for digital input signals | 0 |
Supply voltage |
Type of voltage of the supply voltage | DC |
Supply voltage 1 at DC | 24 ... 24 V |
Supply voltage 1 at DC rated value | |
minimum permissible | 20.4 V |
maximum permissible | 28.8 V |
Control circuit/ Control |
Type of voltage of the control supply voltage | DC |
Control supply voltage at DC | |
rated value | 20.4 ... 28.8 V |
Control supply voltage 1 | |
at DC rated value | 20.4 ... 28.8 V |
at DC | 24 ... 24 V |
Power loss [W] in auxiliary and control circuit | |
in switching state OFF | |
— with bypass circuit | 1.584 W |
— without bypass circuit | 1.584 W |
in switching state ON | |
— with bypass circuit | 5.6736 W |
— without bypass circuit | 5.674 W |
Installation/ mounting/ dimensions |
Mounting position | vertical, horizontal |
Mounting type | pluggable on terminal module |
Height | 290 mm |
Width | 65 mm |
Depth | 150 mm |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Ambient temperature | |
during operation | 0 ... 60 °C |
during storage | -40 ... +70 °C |
during transport | -40 ... +70 °C |
Relative humidity during operation | 5 ... 95 % |
Communication/ Protocol |
Protocol is supported | |
PROFIBUS DP protocol | Yes |
PROFINET protocol | Yes |
Design of the interface | |
PROFINET protocol | Yes |
Product function Bus communication | Yes |
Protocol is supported | |
AS-interface protocol | No |
Product function | |
supports PROFIenergy measured values | No |
supports PROFIenergy shutdown | No |
address range memory of address range | |
of the inputs | 2 byte |
of the outputs | 2 byte |
Type of electrical connection | |
of the communication interface | via backplane bus |
for communication transmission | via backplane bus |
Connections/Terminals |
Type of electrical connection | |
for main current circuit | screw-type terminals |
Type of electrical connection | |
1 for digital input signals | using control module |
2 for digital input signals | using control module |
Type of electrical connection | |
at the manufacturer-specific device interface | plug |
for main energy infeed | screw-type terminals |
for load-side outgoing feeder | Screw-type terminals |
for main energy transmission | via energy bus |
for supply voltage line-side | via backplane bus |
for supply voltage transmission | via backplane bus |
UL/CSA ratings |
Operating voltage | |
at AC at 60 Hz acc. to CSA and UL rated value | 600 V |