3RK1200-0CQ05-0AA3
AS INTERFACE COMP. MODULE K60,

From SIEMENS

AS-i compact module K60 digital 4 DI, IP67 4 x input, maximum 200 mA 4 x M12 socket Y-II assignment ATEX EX II 3D T60°C IP65X Observe special conditions for safe operation: Suitable protective measures against mechanical damage required. For details, see operating instructions Mounting plate 3RK1901-0CA00 must be ordered separately
General technical data
Design of the productdigital I/O modules for operation in the field, IP67 - K60
Type4 inputs
Design of the slave typestandard slave
I/O configuration0
ID/ID2 code1/F
Number I/O sockets4
Type of electrical connection of the inputs and outputsM12 screw-type terminals
AS interface total current input max270 mA
operating voltage according to AS-Interface spezification26.5 ... 31.6 V
Ground terminalPIN5 of each M12 socket is connected to the grounding wrist strap in the mounting plate using a pin
Addressingfront addressing socket
ApplicationUse in Zone 22 hazardous areas according to Classification II 3D (dusty atmosphere, non-conductive dust), resistance to shock: 1 joule Conformance with Directive 94/9/EC (ATEX) is verified through compliance with the standards EN 50281-1-1 und EN 60947-5-2
Delivery notethe modules are delivered without mounting plate
Sensor supply
Type of voltage supply for power supplyusing AS-Interface
Input voltage20 ... 30 V
Property of the sensor supply Short-circuit and overload resistantYes
Ampacity of the sensor supply for all inputs
at ambient temperature 40 °C200 mA
Inputs
Number of digital inputs4
Type of connection2- and 3-wire technology
Input circuitPNP transistor
Type of voltage of the input voltagesDC
Inputs switching level High min10 V
Input current at digital input
for signal <1> minimum6 mA
with signal <0> maximum1.5 mA
Inputs
sensor supply using AS-Interfaceshort-circuit and overload resistant
socket assignment
— PIN 1sensor supply L+
— PIN 2data input II
— PIN 3sensor supply L-
— PIN 4data input I
— PIN 5ground terminal
Design of the pin assignment of the inputsY-II assignement
Outputs
Number of digital outputs0
Outputs external power supply 24 V DCnot required
Outputs
watchdognot required
Assignment of the data bits
Assignment of data bits
socketPIN 4 = IN1 (D0), PIN 2 = IN2 (D1)
socket 2PIN 4 = IN2 (D1)
socket 3PIN 4 = IN3 (D2) , PIN 2 = IN4 (D3)
socket 4PIN 4 = IN4 (D3)
socket 5not assigned (closed)
socket 6not assigned (closed)
socket 7not assigned (closed)
socket 8not assigned (closed)
Ambient conditions
Ambient temperature
during operation-25 ... +85 °C
during storage-40 ... +85 °C
Protection class IPIP65
Display
Status display
display of I/Osyellow LED
display of Uauxnot required
display of AS-Interface/diagnosticsgreen/red LED
Mechanical data
Width60 mm
Height152 mm
Depth29 mm
Mounting typestandard rail mounting/wall mounting using mounting plate for K60 compact module

External links