3RK1105-1BE04-3CA0
AS-I SAFE.MON. ENH., 2 RO, SCREW, 50MS

From SIEMENS

ASIsafe extended Safety monitor 2 F-RO 2 enabling circuits IP20, with screw terminal removable terminals Safe output relay Response time max. 50 ms Monitor type 4, Version 3 Can be used up to Category 4 (EN954-1) up to PL E (EN ISO 13849-1) up to SIL 3 (IEC 61508)
General technical data:
Design of the productsafety monitor, special version
Protocol is supported AS-interface protocolYes
Type2 enabling circuits
Number of release circuits2
Response time max.ms50
Type of electrical connection of the inputs and outputsscrew terminal
Rated operational current Ie
AC-12, 50/60 Hz 250 VA3
AC-15, 50/60 Hz
— 115 VA3
— 230 VA3
DC-12 (DC-1) 24 VA3
DC-13 (DC-11)
— 24 VA1
— 115 VA0.1
— 230 VA0.05
Equipment marking acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750A
Equipment marking acc. to DIN EN 61346-2F
Ambient conditions:
Ambient temperature
during operation°C-20 ... +60
during storage°C-30 ... +70
Protection class IPIP20
Mechanical data:
Widthmm45
Heightmm108
Depthmm120
Mounting typescrews / standard rail

External links