3RK1100-1CQ01-0AA3
AS-INTERFACE APPLICATION MODULE

From SIEMENS

AS-Interface user module IP67 Phased-out product !!! For further information, please contact our sales department digital, 4 DQ, NPN 4x 1 output 4 x M12 socket
General technical data:
Design of the productdigital I/O modules for operation in the field, IP67 - user modules
Design of the slave typestandard slave
Type4 outputs
I/O configuration8
ID code1
Number I/O sockets4
Protocol is supported AS-interface protocolYes
Type of electrical connection of the inputs and outputsM12 screw-type terminals
AS interface total current input maxmA50
operating voltage according to AS-Interface spezificationV26.5 ... 31.6
Note 1An external additional supply (AUX POWER) of 20 to 30 V DC is required for the supply of the output circuits. The additional supply must comply with VDE 0106 (PELV), protection class III.
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750A
Reference code acc. to DIN EN 61346-2K
Inputs:
Number of digital inputs0
Input circuitNPN
Type of voltage of the input voltagesDC
Outputs:
Number of digital outputs4
Type of voltage of output voltagesDC
Outputs external power supply 24 V DC24 V DC using black flat cable
Output current at digital output for signal <1> Rated valueA1
Outputs aggregate current maxA2
Type of switching outputtransistor
Property of the output Short-circuit proofYes
Outputs
short-ciruit protectionbuilt-in
induction protectionbuilt-in
current carrying capacity DC-12/131 A
Status display
display of I/Osyellow LED
display of AS-Interface/diagnosticsLED 'AS-i' green = OK red = No data traffic flashes red/yellow = zero address flashes red = overload sensor
Assignment of data bits
socketPIN4 = OUT1 (D0), PIN2 = OUT2 (D1)
socket 2PIN4 = OUT2 (D1)
socket 3PIN4 = OUT3 (D2), PIN2 = OUT4 (D3)
socket 4PIN4 = OUT4 (D3)
Ambient conditions:
Ambient temperature
during storage°C-40 ... +85
during operation°C-25 ... +85
Protection class IPIP67
Mechanical data:
Widthmm45
Heightmm80
Depthmm27
Mounting typestandard rail mounting/wall mounting using coupling module
connectionusing contact pins on FK-E or Pg-E coupling module