| Contactor relay, 6 NO + 2 NC, 220 V AC 50 Hz 240 V 60 Hz, Size S00, Ring cable lug connection, Captive auxiliary switch, for SUVA applications |
Product brand name | SIRIUS |
Product designation | Auxiliary contactor |
Product type designation | 3RH2 |
General technical data |
Size of contactor | S00 |
Product extension | |
Auxiliary switch | No |
Insulation voltage | |
with degree of pollution 3 rated value | 690 V |
Degree of pollution | 3 |
Surge voltage resistance rated value | 6 kV |
Protection class IP | |
on the front | IP00 |
Shock resistance at rectangular impulse | |
at AC | 7,3g / 5 ms, 4,7g / 10 ms |
Shock resistance with sine pulse | |
at AC | 11,4g / 5 ms, 7,3g / 10 ms |
Mechanical service life (switching cycles) | |
of contactor typical | 10 000 000 |
Reference code acc. to DIN EN 81346-2 | K |
Reference code acc. to DIN EN 61346-2 | K |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Main circuit |
No-load switching frequency | |
at AC | 10 000 1/h |
at DC | 10 000 1/h |
Control circuit/ Control |
Type of voltage of the control supply voltage | AC |
Control supply voltage at AC | |
at 50 Hz rated value | 220 V |
at 60 Hz rated value | 240 V |
Control supply voltage frequency | |
1 rated value | 50 Hz |
2 rated value | 60 Hz |
Operating range factor control supply voltage rated value of magnet coil at AC | |
at 50 Hz | 0.8 ... 1.1 |
at 60 Hz | 0.85 ... 1.1 |
Apparent pick-up power of magnet coil at AC | 37 V·A |
Inductive power factor with closing power of the coil | 0.8 |
Apparent holding power of magnet coil at AC | 5.7 V·A |
Inductive power factor with the holding power of the coil | 0.25 |
Closing delay | |
at AC | 8 ... 33 ms |
Opening delay | |
at AC | 4 ... 15 ms |
Arcing time | 10 ... 15 ms |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | 2 |
instantaneous contact | 2 |
Number of NO contacts for auxiliary contacts | 6 |
instantaneous contact | 6 |
Identification number and letter for switching elements | 62 E |
Operating current at AC-12 maximum | 10 A |
Operating current at AC-15 | |
at 230 V rated value | 6 A |
at 400 V rated value | 3 A |
at 500 V rated value | 2 A |
at 690 V rated value | 1 A |
Operating current at 1 current path at DC-12 | |
at 24 V rated value | 10 A |
at 110 V rated value | 3 A |
at 220 V rated value | 1 A |
at 440 V rated value | 0.3 A |
at 600 V rated value | 0.15 A |
Operating current with 2 current paths in series at DC-12 | |
at 24 V rated value | 10 A |
at 60 V rated value | 10 A |
at 110 V rated value | 4 A |
at 220 V rated value | 2 A |
at 440 V rated value | 1.3 A |
at 600 V rated value | 0.65 A |
Operating current with 3 current paths in series at DC-12 | |
at 24 V rated value | 10 A |
at 60 V rated value | 10 A |
at 110 V rated value | 10 A |
at 220 V rated value | 3.6 A |
at 440 V rated value | 2.5 A |
at 600 V rated value | 1.8 A |
Operating frequency at DC-12 maximum | 1 000 1/h |
Operating current at 1 current path at DC-13 | |
at 24 V rated value | 6 A |
at 110 V rated value | 1 A |
at 220 V rated value | 0.3 A |
at 440 V rated value | 0.14 A |
at 600 V rated value | 0.1 A |
Operating current with 2 current paths in series at DC-13 | |
at 24 V rated value | 10 A |
at 60 V rated value | 3.5 A |
at 110 V rated value | 1.3 A |
at 220 V rated value | 0.9 A |
at 440 V rated value | 0.2 A |
at 600 V rated value | 0.1 A |
Operating current with 3 current paths in series at DC-13 | |
at 24 V rated value | 10 A |
at 60 V rated value | 4.7 A |
at 110 V rated value | 3 A |
at 220 V rated value | 1.2 A |
at 440 V rated value | 0.5 A |
at 600 V rated value | 0.26 A |
Operating frequency at DC-13 maximum | 1 000 1/h |
Design of the miniature circuit breaker | |
for short-circuit protection of the auxiliary circuit up to 230 V | C characteristic: 6 A; 0.4 kA |
Contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
UL/CSA ratings |
Contact rating of auxiliary contacts according to UL | A600 / Q600 |
Short-circuit protection |
Design of the fuse link | |
for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
Installation/ mounting/ dimensions |
Mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail |
Height | 57.5 mm |
Width | 45 mm |
Depth | 117 mm |
Required spacing | |
with side-by-side mounting | |
— forwards | 10 mm |
— upwards | 10 mm |
— downwards | 10 mm |
— at the side | 0 mm |
for grounded parts | |
— forwards | 10 mm |
— upwards | 10 mm |
— at the side | 6 mm |
— downwards | 10 mm |
for live parts | |
— forwards | 10 mm |
— upwards | 10 mm |
— downwards | 10 mm |
— at the side | 6 mm |
Connections/Terminals |
Type of electrical connection | |
for auxiliary and control current circuit | ring cable connection |
Safety related data |
B10 value | |
with high demand rate acc. to SN 31920 | 1 000 000; With 0.3 x Ie |
Proportion of dangerous failures | |
with low demand rate acc. to SN 31920 | 40 % |
with high demand rate acc. to SN 31920 | 73 % |
Failure rate [FIT] | |
with low demand rate acc. to SN 31920 | 100 FIT |
Product function | |
positively driven operation acc. to IEC 60947-5-1 | Yes |
T1 value for proof test interval or service life acc. to IEC 61508 | 20 y |