| AS-Interface module F90, digital 16 DI (multiplexing) 16 x inputs for 2-wire sensor Connection via Combicon Width 90 mm Combicon connector set 3RX9810-0AA00 must be ordered separately |
General technical data: |
Design of the product | | F90 module - I/O modules for operation in the control cabinet, IP20 |
Type | | 16 inputs |
Design of the slave type | | standard slave |
I/O configuration | | 7 |
ID/ID2 code | | F/F |
Type of electrical connection of the inputs and outputs | | combicon connection |
AS interface total current input max | mA | 70 |
operating voltage according to AS-Interface spezification | V | 26.5 ... 31.6 |
Group signal current carrying capacity Iout max | mA | 25 |
Group signal Output voltage Uout min | V | 20 |
Group signal Output voltage Uout max | V | 30 |
Watchdog | | built-in |
Function blocks | | required |
Note 1 | | The module has four input groups. Each input group has four inputs and a group signal for the voltage supply of the inputs. |
Note 2 | | The input groups are activated individually by setting of the respective group signal by the control system. The switching states of the assigned inputs are then read in. |
Note 3 | | An external additional supply (AUX POWER) of 20 to 30 V DC is required for the supply of the output circuits. The additional supply must comply with VDE 0106 (PELV), protection class III. |
Sensor supply: |
Type of voltage supply for power supply | | using AS-Interface |
Input voltage | V | 20 ... 30 |
Property of the sensor supply Short-circuit and overload resistant | | Yes |
Ampacity of the sensor supply for all inputs at ambient temperature 40 °C | mA | 200 |
Inputs: |
Number of digital inputs | | 16 |
Type of connection | | PNP transistor |
Input circuit | | PNP transistor |
Type of voltage of the input voltages | | DC |
Input current at digital input | | |
for signal <1> minimum | mA | 3 |
Inputs | | |
switching level High min | V | 20 |
sensor supply using AS-Interface | | short-circuit and overload resistant |
connection sensors | | mechanical contacts |
Inputs signal 1 | | |
Uin | V | 20 ... 30 |
Iin min | mA | 3 |
Outputs: |
Number of digital outputs | | 0 |
Property of the output Short-circuit proof | | No |
Status display | | |
display of I/Os | | yellow LEDs |
display of AS-Interface/diagnostics | | green LED |
Assignment of data bits | | |
D0 | | group signal G1 (D0) inputs I 1.1 to I 1.4 (D0 to D3) |
D1 | | group signal G2 (D1) inputs I 2.1 to I 2.4 (D0 to D3) |
D2 | | group signal G3 (D2) inputs I 3.1 to I 3.4 (D0 to D3) |
D3 | | group signal G4 (D3) inputs I 4.1 to I 4.4 (D0 to D3) |
Ambient conditions: |
Ambient temperature | | |
during operation | °C | -25 ... +70 |
during storage | °C | -40 ... +85 |
Protection class IP | | IP20 |
Mechanical data: |
Width | mm | 90 |
Height | mm | 75 |
Depth | mm | 37 |
Mounting type | | 35 mm standard rail mounting |