| AS Interface user module IP67 Phased-out product !!! For further information, please contact our sales department digital, 2DI/2DQ 2 x 1 input, max. 100 mA, PNP 2 x output, 1 A 24 V DC 4 x M12 socket |
General technical data: |
Design of the product | | digital I/O modules for operation in the field, IP67 - user modules |
Design of the slave type | | standard slave |
Type | | 2 inputs / 2 outputs |
I/O configuration | | 3 |
ID code | | 0 |
Number I/O sockets | | 4 |
Protocol is supported AS-interface protocol | | Yes |
Type of electrical connection of the inputs and outputs | | M12 screw-type terminals |
AS interface total current input max | mA | 270 |
operating voltage according to AS-Interface spezification | V | 26.5 ... 31.6 |
Note 1 | | An external additional supply (AUX POWER) of 20 to 30 V DC is required for the supply of the output circuits. The additional supply must comply with VDE 0106 (PELV), protection class III. |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | | A |
Reference code acc. to DIN EN 61346-2 | | K |
Inputs: |
Number of digital inputs | | 2 |
Input circuit | | PNP |
Type of voltage of the input voltages | | DC |
Input voltage | V | 20 ... 30 |
Inputs switching level High min | V | 10 |
Input current at digital input | | |
for signal <1> minimum | mA | 5 |
with signal <0> maximum | mA | 1.5 |
Inputs sensor supply using AS-Interface | | short-circuit and overload resistant |
Outputs: |
Number of digital outputs | | 2 |
Type of voltage of output voltages | | DC |
Outputs external power supply 24 V DC | | 24 V DC using black flat cable |
Output voltage at DC at 24 V | V | 22 ... 24 |
Output current at digital output for signal <1> Rated value | A | 2 |
Outputs aggregate current max | A | 2 |
Type of switching output | | transistor |
Property of the output Short-circuit proof | | Yes |
Outputs | | |
short-ciruit protection | | built-in |
induction protection | | built-in |
current carrying capacity DC-12/13 | | 2 A |
Status display | | |
display of I/Os | | yellow LED |
display of AS-Interface/diagnostics | | green LED |
Assignment of data bits | | |
socket | | input (D0) |
socket 2 | | input (D1) |
socket 3 | | output (D2) |
socket 4 | | output (D3) |
Ambient conditions: |
Ambient temperature | | |
during storage | °C | -40 ... +85 |
during operation | °C | -25 ... +85 |
Protection class IP | | IP67 |
Mechanical data: |
Width | mm | 45 |
Height | mm | 80 |
Depth | mm | 27 |
Mounting type | | standard rail mounting/wall mounting using coupling module |
connection | | using contact pins on FK-E or Pg-E coupling module |
Type of connection | | 2- and 3-wire technology |