| Converter Control supply voltage 24 V AC/DC for semiconductor relay / contactor |
General technical data |
Product brand name | | SIRIUS |
Product designation | | converter |
Product function | | solid-state relay / solid-state contactor 3RF2 |
Number of poles for main current circuit | | 0 |
Protection class IP | | IP20 |
Ambient temperature | | |
during operation | °C | -25 ... +60 |
during storage | °C | -55 ... +80 |
Installation altitude at height above sea level maximum | m | 1 000 |
Vibration resistance acc. to IEC 60068-2-6 | | 2g |
Shock resistance acc. to IEC 60068-2-27 | | 15g / 11 ms |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | | U |
Reference code acc. to DIN EN 61346-2 | | T |
Main circuit |
Number of NO contacts for main contacts | | 0 |
Number of NC contacts for main contacts | | 0 |
Derating temperature | °C | 40 |
Operating frequency rated value | Hz | 50 ... 60 |
Relative symmetrical tolerance of the operating frequency | % | 10 |
Control circuit/ Control |
Type of voltage | | AC/DC |
Control supply voltage | | |
at DC | | |
— rated value | V | 18 ... 30 |
at AC | | |
— at 50 Hz | | |
— rated value | V | 20.5 ... 26.5 |
— at 60 Hz | | |
— rated value | V | 20.5 ... 26.5 |
Supply voltage frequency for auxiliary and control current circuit rated value | Hz | 50 ... 60 |
Symmetrical line frequency tolerance | Hz | 5 |
Relative symmetrical tolerance of the supply voltage frequency | % | 10 |
Control current | | |
at AC rated value | mA | 25 |
at DC rated value | mA | 25 |
Operating voltage at the analog input | V | -2 ... +10 |
Source resistance at the analog input | Ω | 100 000 |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | | 0 |
Number of NO contacts for auxiliary contacts | | 0 |
Number of CO contacts for auxiliary contacts | | 0 |
Installation/ mounting/ dimensions |
Mounting type | | clip-on |
Mounting type Side-by-side mounting | | Yes |
Width | mm | 22.5 |
Height | mm | 83.5 |
Depth | mm | 38 |
Connections/Terminals |
Type of electrical connection | | |
for auxiliary and control current circuit | | screw-type terminals |
Design of the thread of the connection screw of the auxiliary and control contacts | | M3 |
Type of connectable conductor cross-sections | | |
for auxiliary and control contacts | | |
— solid | | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²) |
— finely stranded | | |
— with core end processing | | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²) |
— without core end processing | | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²) |
at AWG conductors for auxiliary and control contacts | | 1x (AWG 20 ... 12) |
Connectable conductor cross-section for auxiliary and control contacts | | |
solid | mm² | 0.5 ... 2.5 |
finely stranded | | |
— with core end processing | mm² | 0.5 ... 2.5 |
— without core end processing | mm² | 0.5 ... 2.5 |
AWG number as coded connectable conductor cross section for auxiliary and control contacts | | 12 ... 20 |
Wire stripping length of the cable for auxiliary and control contacts | mm | 7 |
Tightening torque for auxiliary and control contacts with screw-type terminals | N·m | 0.5 ... 0.6 |
Tightening torque [lbf·in] for auxiliary and control contacts with screw-type terminals | lbf·in | 4.5 ... 5.3 |