| Load feeder fuseless Reversing operation, 400 V AC 1.1...1.6 A, 24 V AC Size S00 Screw terminal Type of coordination 2, Iq = 50 kA !!! Phased-out product !!! Successor is SIRIUS 3RA2 |
Product brand name | SIRIUS |
Product designation | non-fused load feeder |
Design of the product | reversing starter |
Manufacturer's article number | |
of the supplied contactor | |
of the supplied circuit-breakers | |
of the supplied RH assembly kit | |
of the supplied link module | |
General technical data |
Size of load feeder | S00 |
Product extension Auxiliary switch | Yes |
Insulation voltage | |
rated value | 690 V |
Degree of pollution | 3 |
Surge voltage resistance rated value | 6 kV |
Protection class IP | |
on the front | IP20 |
Shock resistance | 9.8g |
Mechanical service life (switching cycles) | |
of contactor typical | 10 000 000 |
Type of assignment | 2 |
Certificate of suitability | UL / CSA / CCC / GL / LRS / BV / DNV / PRS |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | Q |
Reference code acc. to DIN EN 81346-2 | Q |
Reference code acc. to DIN EN 61346-2 | Q |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Main circuit |
Number of poles for main current circuit | 3 |
Design of the switching contact | electromechanical |
Adjustable pick-up value current of the current-dependent overload release | 1.1 ... 1.6 A |
Type of the motor protection | bimetal |
Operating voltage | |
at AC-3 rated value maximum | 690 V |
Operating current | |
at AC-3 | |
— at 400 V rated value | 1.5 A |
Operating power | |
at AC-3 | |
— at 400 V rated value | 0.55 kW |
No-load switching frequency | 15 1/s |
Control circuit/ Control |
Type of voltage of the control supply voltage | AC |
Control supply voltage 1 at AC | |
at 50 Hz rated value | 24 V |
Control supply voltage frequency | |
1 rated value | 50 Hz |
Auxiliary circuit |
Number of NC contacts for auxiliary contacts | 0 |
Number of NO contacts for auxiliary contacts | 0 |
Number of CO contacts | |
for auxiliary contacts | 0 |
Protective and monitoring functions |
Maximum short-circuit current breaking capacity (Icu) | |
at 400 V rated value | 50 kA |
Short-circuit protection |
Product function Short circuit protection | Yes |
Design of short-circuit protection | circuit-breakers |
Installation/ mounting/ dimensions |
Mounting position | horizontal |
| |
(mounting type) | snap-on fastening on 35 mm standard rail |
Height | 159 mm |
Width | 90 mm |
Depth | 75 mm |
Required spacing | |
with side-by-side mounting | |
— at the side | 0 mm |
for grounded parts | |
— forwards | 10 mm |
— Backwards | 0 mm |
— upwards | 20 mm |
— at the side | 9 mm |
for live parts | |
— forwards | 10 mm |
— Backwards | 9 mm |
— downwards | 0 mm |
— at the side | 20 mm |
Connections/Terminals |
Type of electrical connection | |
for main current circuit | screw-type terminals |
Type of connectable conductor cross-sections | |
for main contacts | |
— solid | 0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²) |
— stranded | 0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²) |
— finely stranded with core end processing | 0.5 ... 2.5 mm², 2x (0.5 ... 2.5 mm²) |
at AWG conductors for main contacts | 2x (18 ... 14) |
Connectable conductor cross-section for main contacts | |
single or multi-stranded | 0.5 ... 4 mm² |
stranded | 0.5 ... 4 mm² |
finely stranded with core end processing | 0.5 ... 2.5 mm² |
AWG number as coded connectable conductor cross section | |
for main contacts | 18 ... 14 |
Communication/ Protocol |
Protocol is supported | |
PROFIBUS DP protocol | No |
PROFINET protocol | No |
Product function Bus communication | No |
Protocol is supported | |
AS-interface protocol | No |
Inputs/ Outputs |
Number of digital inputs | 0 |