3NP4476-1CG01
fuse switch disconnector 3NP4

From SIEMENS

SENTRON, Fuse switch disconnector 3NP4, 3-pole, NH3, 630 A, for Busbar system 8US 60 mm, screw terminal
Model
Product brand nameSENTRON
Product designation3NP4 fuse switch disconnector
Design typeFor snapping on 60 mm busbar systems, without high-speed closing
Design of the operating mechanismCover handle
Design of the load switch / Strip formNo
General technical data
Number of poles3
Size of disconnecting linkNH2, NH3
Size of fuse linkNH2, NH3
Continuous current / at 35 °C / rated value630 A
power factor cos phi / in utilization category
AC-21 B / at 400 V0.95
AC-21 B / at 500 V0.95
AC-22 B / at 400 V0.65
AC-22 B / at 500 V0.65
circuit-breaker / Design3NP447
Mounting typePlug-in
Fuse systemLV HRC fuse
Voltage
Type of voltageAC/DC
Insulation voltage / rated value800 V
Surge voltage resistance / rated value6 kV
Protection class
Protection class IP / on the frontIP00
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole15.6 W
Electricity
Current / rated value630 A
Continuous current
rated value630 A
at 40 °C / rated value617 A
at 45 °C / rated value611 A
at 50 °C / rated value592 A
at 55 °C / rated value567 A
at 60 °C / rated value536 A
at 65 °C / rated value504 A
at 70 °C / rated value473 A
Let-through current / I2 t / maximum permissible / in utilization category
AC-21 B / at 400 V5 500 000 A²·s
AC-21 B / at 500 V5 500 000 A²·s
AC-22 B / at 400 V5 500 000 A²·s
AC-22 B / at 500 V5 500 000 A²·s
Let-through current / Ic / maximum permissible / in utilization category
AC-21 B / at 400 V55 kA
AC-21 B / at 500 V50 kA
AC-22 B / at 400 V55 kA
AC-22 B / at 500 V50 kA
Main circuit
Operating voltage
at AC / at 50/60 Hz / rated value690 V
at AC / rated value / maximum690 V
at DC / rated value440 V
Rated current Ie / maximum / in utilization category
AC-21 B / at 400 V630 A
AC-21 B / at 500 V630 A
AC-22 B / at 400 V630 A
AC-22 B / at 500 V630 A
Suitability
Suitability for usesystem protection
Main switchNo
switch disconnectorYes
EMERGENCY OFF switchNo
safety switchYes
Product function
Product function / fuse monitoringNo
Short circuit
Maximum short-circuit current breaking capacity (Icu) / at 400 V / rated value5.04 kA
Conditional rated short-circuit current / in utilization category
AC-21 B / at 400 V50 kA
AC-21 B / at 500 V50 kA
AC-22 B / at 400 V50 kA
AC-22 B / at 500 V50 kA
Connections
Type of electrical connection2 - 240 mm²
for main current circuitscrew-type terminals
Mechanical Design
Height300 mm
Width256 mm
Depth187 mm
Number of width units1
Mounting typeBusbar
Mounting type
floor mountingNo
front mountingNo
rail mountingYes
Busbar center-to-center spacing60 mm
Net weight7 578 g
Environmental conditions
Degree of pollution3
Installation altitude / at height above sea level / maximum2 000 m
Ambient temperature
during operation / minimum-25 °C
during operation / maximum55 °C
during storage / minimum-50 °C
during storage / maximum80 °C

External links