| SENTRON, Fuse switch disconnector 3NP4, 3-pole, NH000, 160 A, for assembly and installation on mounting plate, box terminal, can also be snapped onto standard mounting rail 35 mm |
Model |
Product brand name | SENTRON |
Product designation | 3NP4 fuse switch disconnector |
Design of the product | Can also be snapped onto standard mounting rail 35 mm |
Design type | For assembly and installation, can also be snapped on 35 mm DIN rail, without high-speed closing |
Design of the operating mechanism | Cover handle |
Design of the load switch / Strip form | No |
General technical data |
Number of poles | 3 |
Size of disconnecting link | NH000 |
Size of fuse link | NH000 |
Continuous current / at 35 °C / rated value | 160 A |
power factor cos phi / in utilization category | |
AC-21 B / at 400 V | 0.95 |
AC-21 B / at 500 V | 0.95 |
AC-22 B / at 400 V | 0.65 |
AC-22 B / at 500 V | 0.65 |
circuit-breaker / Design | 3NP401 |
Mounting type | Fixed mounting |
Fuse system | LV HRC fuse |
Voltage |
Type of voltage | AC/DC |
Insulation voltage / rated value | 690 V |
Surge voltage resistance / rated value | 6 kV |
Protection class |
Protection class IP / on the front | IP00 |
Dissipation |
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 1.66 W |
Electricity |
Current / rated value | 160 A |
Continuous current | |
rated value | 160 A |
at 40 °C / rated value | 160 A |
at 45 °C / rated value | 157 A |
at 50 °C / rated value | 154 A |
at 55 °C / rated value | 146 A |
at 60 °C / rated value | 139 A |
at 65 °C / rated value | 131 A |
Let-through current / I2 t / maximum permissible / in utilization category | |
AC-21 B / at 400 V | 130 000 A²·s |
AC-21 B / at 500 V | 80 000 A²·s |
AC-22 B / at 400 V | 130 000 A²·s |
AC-22 B / at 500 V | 80 000 A²·s |
Let-through current / Ic / maximum permissible / in utilization category | |
AC-21 B / at 400 V | 15 kA |
AC-21 B / at 500 V | 10 kA |
AC-22 B / at 400 V | 15 kA |
AC-22 B / at 500 V | 10 kA |
Main circuit |
Operating voltage | |
at AC / at 50/60 Hz / rated value | 690 V |
at AC / rated value / maximum | 690 V |
at DC / rated value | 220 V |
Rated current Ie / maximum / in utilization category | |
AC-21 B / at 400 V | 160 A |
AC-21 B / at 500 V | 160 A |
AC-22 B / at 400 V | 160 A |
AC-22 B / at 500 V | 100 A |
Suitability |
Suitability for use | system protection |
Main switch | No |
switch disconnector | Yes |
EMERGENCY OFF switch | No |
safety switch | Yes |
Product function |
Product function / fuse monitoring | No |
Short circuit |
Maximum short-circuit current breaking capacity (Icu) / at 400 V / rated value | 0.8 kA |
Conditional rated short-circuit current / in utilization category | |
AC-21 B / at 400 V | 50 kA |
AC-21 B / at 500 V | 50 kA |
AC-22 B / at 400 V | 50 kA |
AC-22 B / at 500 V | 50 kA |
Connections |
Type of electrical connection | 1.5 - 50 mm² |
for main current circuit | box terminal |
Mechanical Design |
Height | 143 mm |
Width | 89 mm |
Depth | 73.5 mm |
Number of width units | 1 |
Mounting type | Mounting plate |
Mounting type | |
floor mounting | Yes |
front mounting | No |
rail mounting | No |
Net weight | 504 g |
Environmental conditions |
Degree of pollution | 3 |
Installation altitude / at height above sea level / maximum | 2 000 m |
Ambient temperature | |
during operation / minimum | -25 °C |
during operation / maximum | 55 °C |
during storage / minimum | -50 °C |
during storage / maximum | 80 °C |