| PLUG-IN SWITCH DISCONNECT STRIP FOR NH FUSES 3-POLE, SIZE 2, I=400A, U=690V WITH SINGLE-BREAK WITH CABLE TERMINAL CONNECTION WITH ELECTRON. FUSE MONITORING |
Model |
Product designation | Switch Disconnector with Fuses 3NJ61 |
version | With single disconnection and fuse monitoring |
Design type | plug-in to busbars with 185mm center-line spacing |
Type of switching contact / double breaking switching contact | Yes |
Design of the load switch / Strip form | Yes |
Design of the switching contact | mechanical |
General technical data |
Number of poles | 3 |
Field of application | LINE PROTECTION |
Size of disconnecting link | 2 |
Size of fuse link | 2 |
power factor cos phi / in utilization category | |
AC-21 B / at 400 V | 0.95 |
AC-22 B / at 400 V | 0.65 |
AC-22 B / at 500 V | 0.65 |
circuit-breaker / Design | 3NJ614 |
Reference code / acc. to DIN 40719 extended according to IEC 204-2 / acc. to IEC 750 | Q |
Fuse system | LV HRC fuse |
Voltage |
Rated operational voltage Ue / max. | 690 V |
Rated insulation voltage Ui | 1 000 V |
Surge voltage resistance / rated value | 8 000 V |
Protection class |
Protection class IP | IP41 |
Electricity |
rated current In | |
max. | 400 A |
at 35 Cel | 400 A |
at 40 Cel | 380 A |
at 45 Cel | 360 A |
at 50 Cel | 340 A |
Continuous current / rated value | 400 A |
Let-through current / I2 t / maximum permissible / in utilization category | |
AC-21 B / at 400 V | 2 150 000 A²·s |
AC-21 B / at 500 V | 2 150 000 A²·s |
AC-22 B / at 400 V | 2 150 000 A²·s |
AC-22 B / at 500 V | 2 150 000 A²·s |
Let-through current / Ic / maximum permissible / in utilization category | |
AC-21 B / at 400 V | 32 kA |
AC-21 B / at 500 V | 32 kA |
AC-22 B / at 400 V | 32 kA |
AC-22 B / at 500 V | 32 kA |
Main circuit |
Operating voltage | |
at AC / at 50/60 Hz / rated value | 690 V |
Rated current Ie / maximum / in utilization category | |
AC-21 B / at 400 V | 400 A |
AC-21 B / at 500 V | 400 A |
AC-22 B / at 400 V | 400 A |
AC-22 B / at 500 V | 400 A |
Short circuit |
Maximum short-circuit current breaking capacity (Icu) / at 400 V / rated value | 50 kA |
Conditional rated short-circuit current / in utilization category | |
AC-21 B / at 400 V | 50 kA |
AC-21 B / at 500 V | 50 kA |
AC-22 B / at 400 V | 50 kA |
AC-22 B / at 500 V | 50 kA |
Connections |
Type of connection, main circuit | Stud terminal, 2xM12 |
Type of electrical connection / for main current circuit | stud terminals |
Mechanical Design |
Height | 308 mm |
Width | 590 mm |
Depth | 198 mm |
Type of mounting | plug-in version |
Mounting type | clip-on |
Busbar center-to-center spacing | 185 mm |
Busbar center-to-center spacing | |
40 mm | No |
50 mm | No |
60 mm | No |
100 mm | No |
185 mm | Yes |
Environmental conditions |
Installation altitude / at height above sea level / maximum | 2 000 m |
Ambient temperature | |
during operation / minimum | -25 °C |
during operation / maximum | 55 °C |