3KL5530-1AA01
SWITCH DISCONNECTOR WITH FUSE

From SIEMENS

Switch disconnector with fuse in new design Iu=250 A, Ue = 690 V, 3-pole for LV HRC fuse Sz. 1 and 2 basic version without 8UC6 handle and shaft without lyra contacts
Model
Product brand nameSENTRON
versionBasic version without handle
Design typeFor mounting and installation
Design of the operating mechanismmanual operating mechanism
Design of the load switch / Strip formNo
Type of the driving mechanism / motor driveNo
Number of poles3
Size of disconnecting link2 and 1
Fuse systemLV HRC fuse
Insulation voltage / rated value1 000 V
Surge voltage resistance / rated value8 000 V
Protection class
Protection class IPIP00
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole11 W
Electricity
Operating current / at AC-21 / rated value250 A
Continuous current / rated value250 A
Let-through current / I2 t / maximum permissible / in utilization category / AC-22 B / at 400 V1 000 000 A²·s
Main circuit
Number of poles / for main current circuit3
Operating power
at AC-23 A / at 400 V / at 50/60 Hz / rated value132 000 W
at AC-23 A / at 500 V / at 50/60 Hz / rated value132 000 W
at AC-23 A / at 690 V / at 50/60 Hz / rated value185 000 W
Operating voltage
at AC / at 50/60 Hz / rated value690 V
at DC / rated value440 V
Rated current Ie / maximum / in utilization category
AC-21 A / at 400 V250 A
AC-21 A / at 500 V250 A
AC-21 B / at 400 V250 A
AC-21 B / at 500 V250 A
AC-22 A / at 400 V250 A
AC-22 A / at 500 V250 A
AC-22 B / at 400 V250 A
AC-22 B / at 500 V250 A
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Number of NC contacts / for auxiliary contacts0
Number of NO contacts / for auxiliary contacts0
Product feature / interlockYes
Short circuit
Conditional rated short-circuit current
400V80 kA
500V80 kA
in utilization category / AC-21 A / at 400 V80 kA
in utilization category / AC-21 A / at 500 V80 kA
in utilization category / AC-21 B / at 400 V80 kA
in utilization category / AC-21 B / at 500 V80 kA
in utilization category / AC-22 A / at 400 V80 kA
in utilization category / AC-22 A / at 500 V80 kA
in utilization category / AC-22 B / at 400 V80 kA
in utilization category / AC-22 B / at 500 V80 kA
Connections
Connectable conductor cross-section
for main contacts
— stranded / maximum150 mm²
Type of connection, main circuitflat pad connection, M10
Type of electrical connection
for main current circuitflat connector
Mechanical Design
Height160 mm
Width247 mm
Depth209 mm
Type of mountingfixed mounted
Mounting positionany
Mounting typeSurface mounting and installation
Mounting type
front mounting with 4-hole attachmentNo
front mounting with central attachmentNo
rail mountingNo
Environmental conditions
Ambient temperature
during operation / minimum-25 °C
during operation / maximum55 °C
during storage / minimum-50 °C
during storage / maximum80 °C