| Switch disconnector with fuse in new design Iu=160 A, Ue = 690 V, 3-pole for LV HRC fuse Sz. 00 basic version without 8UC6 handle and shaft |
Model |
Product brand name | SENTRON |
version | Basic version without handle |
Design type | For mounting and installation |
Design of the operating mechanism | manual operating mechanism |
Design of the load switch / Strip form | No |
Type of the driving mechanism / motor drive | No |
Number of poles | 3 |
Size of disconnecting link | 00 and 000 |
Fuse system | LV HRC fuse |
Insulation voltage / rated value | 1 000 V |
Surge voltage resistance / rated value | 8 000 V |
Protection class |
Protection class IP | IP00 |
Dissipation |
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 12 W |
Electricity |
Operating current / at AC-21 / rated value | 160 A |
Continuous current / rated value | 160 A |
Let-through current / I2 t / maximum permissible / in utilization category / AC-22 B / at 400 V | 223 000 A²·s |
Main circuit |
Number of poles / for main current circuit | 3 |
Operating power | |
at AC-23 A / at 400 V / at 50/60 Hz / rated value | 80 000 W |
at AC-23 A / at 500 V / at 50/60 Hz / rated value | 80 000 W |
at AC-23 A / at 690 V / at 50/60 Hz / rated value | 110 000 W |
Operating voltage | |
at AC / at 50/60 Hz / rated value | 690 V |
at DC / rated value | 440 V |
Rated current Ie / maximum / in utilization category | |
AC-21 A / at 400 V | 160 A |
AC-21 A / at 500 V | 160 A |
AC-21 B / at 400 V | 160 A |
AC-21 B / at 500 V | 160 A |
AC-22 A / at 400 V | 160 A |
AC-22 A / at 500 V | 160 A |
AC-22 B / at 400 V | 160 A |
AC-22 B / at 500 V | 160 A |
Auxiliary circuit |
Number of CO contacts / for auxiliary contacts | 0 |
Number of NC contacts / for auxiliary contacts | 0 |
Number of NO contacts / for auxiliary contacts | 0 |
Product feature / interlock | Yes |
Short circuit |
Conditional rated short-circuit current | |
400V | 100 kA |
500V | 100 kA |
in utilization category / AC-21 A / at 400 V | 100 kA |
in utilization category / AC-21 A / at 500 V | 100 kA |
in utilization category / AC-21 B / at 400 V | 100 kA |
in utilization category / AC-21 B / at 500 V | 100 kA |
in utilization category / AC-22 A / at 400 V | 100 kA |
in utilization category / AC-22 A / at 500 V | 100 kA |
in utilization category / AC-22 B / at 400 V | 100 kA |
in utilization category / AC-22 B / at 500 V | 100 kA |
Connections |
Connectable conductor cross-section | |
for main contacts | |
— stranded / maximum | 120 mm² |
Type of connection, main circuit | flat pad connection, M8 |
Type of electrical connection | |
for main current circuit | flat connector |
Mechanical Design |
Height | 125 mm |
Width | 185 mm |
Depth | 143 mm |
Type of mounting | fixed mounted |
Mounting position | any |
Mounting type | Surface mounting and installation |
Mounting type | |
front mounting with 4-hole attachment | No |
front mounting with central attachment | No |
rail mounting | No |
Environmental conditions |
Ambient temperature | |
during operation / minimum | 185 °C |
during operation / maximum | -25 °C |
during storage / minimum | -50 °C |
during storage / maximum | 80 °C |