3KL5330-1AB01
SW.DISCON. W.F. 3-P 160A/SZ.00

From SIEMENS

Switch disconnector with fuse in new design Iu=160 A, Ue = 690 V, 3-pole for LV HRC fuse Sz. 00 basic version without 8UC6 handle and shaft
Model
Product brand nameSENTRON
versionBasic version without handle
Design typeFor mounting and installation
Design of the operating mechanismmanual operating mechanism
Design of the load switch / Strip formNo
Type of the driving mechanism / motor driveNo
Number of poles3
Size of disconnecting link00 and 000
Fuse systemLV HRC fuse
Insulation voltage / rated value1 000 V
Surge voltage resistance / rated value8 000 V
Protection class
Protection class IPIP00
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole12 W
Electricity
Operating current / at AC-21 / rated value160 A
Continuous current / rated value160 A
Let-through current / I2 t / maximum permissible / in utilization category / AC-22 B / at 400 V223 000 A²·s
Main circuit
Number of poles / for main current circuit3
Operating power
at AC-23 A / at 400 V / at 50/60 Hz / rated value80 000 W
at AC-23 A / at 500 V / at 50/60 Hz / rated value80 000 W
at AC-23 A / at 690 V / at 50/60 Hz / rated value110 000 W
Operating voltage
at AC / at 50/60 Hz / rated value690 V
at DC / rated value440 V
Rated current Ie / maximum / in utilization category
AC-21 A / at 400 V160 A
AC-21 A / at 500 V160 A
AC-21 B / at 400 V160 A
AC-21 B / at 500 V160 A
AC-22 A / at 400 V160 A
AC-22 A / at 500 V160 A
AC-22 B / at 400 V160 A
AC-22 B / at 500 V160 A
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Number of NC contacts / for auxiliary contacts0
Number of NO contacts / for auxiliary contacts0
Product feature / interlockYes
Short circuit
Conditional rated short-circuit current
400V100 kA
500V100 kA
in utilization category / AC-21 A / at 400 V100 kA
in utilization category / AC-21 A / at 500 V100 kA
in utilization category / AC-21 B / at 400 V100 kA
in utilization category / AC-21 B / at 500 V100 kA
in utilization category / AC-22 A / at 400 V100 kA
in utilization category / AC-22 A / at 500 V100 kA
in utilization category / AC-22 B / at 400 V100 kA
in utilization category / AC-22 B / at 500 V100 kA
Connections
Connectable conductor cross-section
for main contacts
— stranded / maximum120 mm²
Type of connection, main circuitflat pad connection, M8
Type of electrical connection
for main current circuitflat connector
Mechanical Design
Height125 mm
Width185 mm
Depth143 mm
Type of mountingfixed mounted
Mounting positionany
Mounting typeSurface mounting and installation
Mounting type
front mounting with 4-hole attachmentNo
front mounting with central attachmentNo
rail mountingNo
Environmental conditions
Ambient temperature
during operation / minimum185 °C
during operation / maximum-25 °C
during storage / minimum-50 °C
during storage / maximum80 °C

External links